Control Systems
172
VI
VI
Building management system
(8) BACnet Gateway
(9) Digital input / output
2. DMS B-net (BACnet GW)
7) Object list
MIM-B17N
BACnet Gateway has following point list.
Digital input / output Gateway has following point list.
Instance
Number
Control and
Monitoring
Object
Type
Object Name
Status value
1
All device OFF
BO
ALL_OFF_xx
Inactive : All devices Off
1
DMS2 Status
AI
DMS2_Status_xx
/PSNBM&NFSHFODZTUPQ
5SBDLJOHJOQSPHSFTT
5SBDLJOHGBJMFE
%.4
¥
BACnet
Communication failed
1
BACnet error code
AI
BACnetApp_Error_
Code_xx
BACnet error code
2
Gateway Notify
NC
GW_Notify_xx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1
Text-2
Text-3
Text-4
Text-5
1
Digital Input 1
BI
%*@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off
On
2
Digital Input 2
BI
%*@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off
On
3
Digital Input 3
BI
%*@@YY@YY
Off
On
4
Digital Input 4
BI
%*@@YY@YY
Off
On
5
Digital Input 5
BI
%*@@YY@YY
Off
On
6
Digital Input 6
BI
%*@@YY@YY
Off
On
7
Digital Input 7
BI
%*@@YY@YY
Off
On
8
Digital Input 8
BI
%*@@YY@YY
Off
On
9
Digital Input 9
BI
%*@@YY@YY
Off
On
Digital Input 10
BI
%*@@YY@YY
Off
On
11
Digital Output 1
BO
%0@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off
On
12
Digital Output 2
BO
%0@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off
On
13
Digital Output 3
BO
%0@@YY@YY
Off
On
14
Digital Output 4
BO
%0@@YY@YY
Off
On
15
Digital Output 5
BO
%0@@YY@YY
Off
On
16
Digital Output 6
BO
%0@@YY@YY
Off
On
17
Digital Output 7
BO
%0@@YY@YY
Off
On
18
Digital Output 8
BO
%0@@YY@YY
Off
On
f
Caution
t
You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
t
If communication error occurs on devices such as SIM/OnOff Controller/Interface Module etc, other functions such as
power distribution may also create a problem. You must have BMS system to check the errors and you must take action
immediately.