Control Systems
168
VI
VI
Building management system
(2) AHU kit
2. DMS B-net (BACnet GW)
7) Object list
MIM-B17N
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive
Active
Text-1
Text-2
Text-3
Text-4
Text-5
1
Indoor Temperature
AI
AHU_RoomTemp_xx_xxxxxx
℃
2
Set temperature
AV
AHU_Temp_Set_xx_xxxxxx
℃
3
Setting lower temperature limit
AV
AHU_Cool_LimitTemp_xx_xxxxxx
℃
4
Setting upper temperature limit
AV
AHU_Heat_LimitTemp_xx_xxxxxx
℃
5
The power value of an indoor
unit after the basic date
AI
AHU_Baseline_kWh_xx_xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI
AHU_Baseline_Minute_xx_xxxxxx
Minute
7
Power value within period
AI
")6@1FSJPE@L8I@YY@YYYYYY
kWh
8
The number of hours usage of
an indoor unit within period
AI
")6@[email protected]@YY@YYYYYY
Minute
9
Power On/Off
BV
")6@1PXFS@YY@YYYYYY
Off
On
Applying lower temperature
limit setting
BV
AHU_Cool_Limit_set_xx_xxxxxx
False
True
11
Applying upper temperature
limit setting
BV
AHU_Heat_Limit_set_xx_xxxxxx
False
True
12
Filter sign status
BI
AHU_FilterSign_xx_xxxxxx
False
True
13
Filter sign reset
BO
AHU_FilterSign_Reset_xx_xxxxxx
False
True
14
Operation mode status
MV
AHU_Operation_Mode_xx_xxxxxx
Auto
Cool
Heat
Fan
Dry
15
Operation mode limit status
MV
AHU_Mode_Limit_xx_xxxxxx
No
Limit
Cool
Only
Heat
Only
16
Remote controller limit status
MV
AHU_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
17
Integrated error code of both
indoor unit and outdoor unit
AI
AHU_Error_Code_xx_xxxxxx
Refer to Samsung integrated error code list
18
(
7
)
Discharge cooling set
temperature
AV
AHU_DisCoolSetTemp_xx_xxxxxx
°C
19
(
7
)
Discharge heating set
temperature
AV
AHU_DisHeatSetTemp_xx_xxxxxx
°C
(
7
)
Discharge current
temperature
AI
AHU_Dis_CurrentTemp_xx_xxxxxx
°C
21
(
7
)
Humidification setting
BV
AHU_Humidification_xx_xxxxxx
Off
On
22
(
7
)
Outdoor air intake setting
BV
AHU_OAIntake_xx_xxxxxx
Off
On
23
(
7
)
Outdoor cooling setting
BV
AHU_OutdoorCool_xx_xxxxxx
Off
On
24
(
7
)
Fan speed status
MV
AHU_FanSpeed_xx_xxxxxx
Low
Mid
High
25
(
7
)
Set humidity status
MV
AHU_SetHumidity_xx_xxxxxx
Low
Mid
High
26
(
7
)
Current humidity status
MI
AHU_CurrentHumidity_xx_xxxxxx
Low
Mid
High
27
AHU Notify
NC
AHU_Notify_xx_xxxxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
(
7
)
Mark is optionally supported.
Single AHU unit has following point list.