Control Systems
170
VI
VI
Building management system
(4) EHS
2. DMS B-net (BACnet GW)
7) Object list
MIM-B17N
Force hot water mode (
7
marked) will be supported later. It is the point list of Hydro Unit and Hydro Unit HT.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive
Active
Text-1
Text-2
Text-3
Text-4
1
Room temperature
AI
EHS_RoomTemp_xx_xxxxxx
°C
2
Set temperature
AV
EHS_Temp_Set_xx_xxxxxx
°C
Use when displayed temperature type is set
to 'Room'.
3
Set temperature of water out
AV
EHS_WaterOutTemp_Set_xx_xxxxxx
°C
Use when displayed temperature type is set
to 'WaterOut'.
4
Set temperature of hot water
AV
EHS_HotWaterTemp_Set_xx_xxxxxx
°C
5
Setting lower temperature limit
AV
EHS_Cool_LimitTemp_xx_xxxxxx
°C
Use when displayed temperature type is set
to 'Room'.
6
Setting upper temperature limit
AV
EHS_Heat_LimitTemp_xx_xxxxxx
°C
Use when displayed temperature type is set
to 'Room'.
7
Lower temperature limit for water out
AV
EHS_WOCoolLimitTemp_xx_xxxxxx
°C
8
Upper temperature limit for water out
AV
EHS_WOHeatLimitTemp_xx_xxxxxx
°C
9
Upper temperature limit for hot water
AV
EHS_WTHeatlLimitTemp_xx_xxxxxx
°C
The power value after the basic date
AI
EHS_Baseline_kWh_xx_xxxxxx
kWh
11
The number of hours usage of an in-
door unit after the basic date
AI
EHS_Baseline_Minute_xx_xxxxxx
Minute
12
1PXFSWBMVFXJUIJOQFSJPE
AI
&)4@1FSJPE@L8I@YY@YYYYYY
kWh
13
The number of hours usage of an in-
door unit within period
AI
&)4@[email protected]@YY@YYYYYY
Minute
14
Current temperature of water out
AI
EHS_WOCurrentTemp_xx_xxxxxx
°C
15
Current temperature of hot water
AI
EHS_HotWaterTemp_xx_xxxxxx
°C
16
Displayed temperature type
BI
EHS_ControlTempType_xx_xxxxxx
Room
WaterOut
17
Thermostat usage
BI
EHS_Thermostat_xx_xxxxxx
False
True
18
Outing
BI
EHS_GoOut_xx_xxxxxx
Off On
19
1PXFS0O0GG
BV
&)4@1PXFS@YY@YYYYYY
Off
On
Setting lower temperature limit
BV
EHS_Cool_LimitTemp_Set_xx_xxxxxx
False
True
Use when displayed tempera-
ture type is set to 'Room'.
21
Setting upper temperature limit
BV
EHS_Heat_LimitTemp_Set_xx_xxxxxx
False
True
Use when displayed tempera-
ture type is set to 'Room'.
22
Apply lower temperature limit for water
out
BV
EHS_WOCoolLimitFlag_xx_xxxxxx
False
True
Use when displayed tempera-
ture type is set to 'WaterOut'.
23
Apply upper temperature limit for water
out
BV
EHS_WOHeatLimitFlag_xx_xxxxxx
False
True
Use when displayed tempera-
ture type is set to 'WaterOut'.
24
Apply upper temperature limit for hot
water
BV
EHS_WTHeatLimitFlag_xx_xxxxxx
False
True
25
On/Off status of hot water mode
BV
&)4@)PU8BUFS@1PXFS@YY@YYYYYY
Off On
26
Status of quiet operation
BV
EHS_Sleep_xx_xxxxxx
Off On
27
Operation mode status
MV
EHS_Operation_Mode_xx_xxxxxx
Auto
Cool
Heat
28
Operation mode limit status
MV
EHS_Mode_Limit_xx_xxxxxx
No Limit
Cool Only
Heat Only
29
Remote controller limit status
MV
EHS_Remocon_Limit_xx_xxxxxx
Enable RC
Disable RC Conditional RC
Status of hot water operation mode
MV
EHS_HotWater_Mode_xx_xxxxxx
* Force
Eco
Standard
1PXFS
31
Integrated error code of both indoor unit
and outdoor unit
AI
EHS_Error_Code_xx_xxxxxx
32
EHS notifiy
NC
EHS_Notify_xx_xxxxxx
When the error occurred, send event to list of destination in
the recipient_list. (Max : 8)
[¥]UwGG ¥UGGGX^W
YWX[TW[TY\GGG㝘䟸G[aZ]a[\