155
B
UILDING
M
ANAGEMENT
S
YSTEM
11) Network variable list
t
Supported NV (Network Variable) is different depending on the connected devices.
No.
NV Name
Description
Indoor
ERV
AHU Kit
1
nviOnOff
ON/OFF command
O
O
O
2
nviApplicMode
Setting operating mode
O
X
O
3
nviSetpoint
Setting desirable temperature
O
X
O
4
nviFanStatus
Setting fan swing and speed
O
O
X
5
nviERVMode
Setting ERV operation mode
X
O
X
6
nviFilterReset
Filter reset command
O
O
O
7
nviUserLockout
Setting the restriction of remote control use
O
O
O
8
nviOccOpMode
Setting cooling only mode / Setting heating only mode
O
X
O
9
nviCoolTempLock
Setting the low temperature limit
O
X
O
10
nviHeatTempLock
Setting the high temperature limit
O
X
O
11
nvoSpaceTemp
Display indoor temperature
O
X
O
12
nvoApplicMode
Display operating mode
O
X
O
13
nvoSetpoint
Display desire temperature
O
X
O
14
nvoOnOff
Display ON/OFF status
O
O
O
15
nvoFanStatus
Display wind speed and direction
O
O
X
16
nvoERVMode
Display ERV operating mode
X
O
X
17
nvoErrorCode
Display Error code
O
O
O
18
nvoDeviceAlarm
Remote control Lock, Filter Sign, Thermo ON/OFF,
Error occurrence status display
O
O
O
19
nvoOccOpMode
Cooling only/Heating only setup status display
O
X
O
20
nvoCoolTempLock
Low temperature limit setting status display
O
X
O
21
nvoHeatTempLock
High temperature limit setting status display
O
X
O
22
nvoUserLockout
Display the restriction of remote control use
O
O
O
23
nvoEnergyConp
Display electricity usage
O
X
X
24
nvoEnergyCon
Monitor total electricity usage
O
X
X
25
nvoRuntimep
%JTQMBZVTFEIPVST 1FSJPE
O
X
O
26
nvoRuntime
Monitor total operation hours
O
X
O
27
nvoDevListDesc
The summary of device information (Model, Address,
Operation Status)
O
O
O
[¥]UwGG ¥UGGGX\\