153
B
UILDING
M
ANAGEMENT
S
YSTEM
9) Network variable
(1) Indoor unit/ ERV/ AHU kit object
No.
Name
Type
M/O
Description
1
nviONOff
SNVT_switch
O
ON/OFF command
2
NviApplicMode
SNVT_hvac_mode
O
Setting operating mode
3
nviSetpoint
SNVT_temp_p
O
Setting desire temperature
4
nviFanStatus
SNVT_switch
O
Setting fan speed
5
nviERVMode
SNVT_count
O
Setting ERV operation mode
6
nviFilterReset
SNVT_switch
O
Filter reset command
7
nviUserLockout
SNVT_switch
O
Setting the restriction of remote control use
8
nviOccOpMode
SNVT_switch
O
Setting cooling only mode / heating only mode
9
nviCoolTempLock
SNVT_switch
O
Setting the low temperature limit
10
nviHeatTempLock
SNVT_switch
O
Setting the high temperature limit
11
nvoSpaceTemp
SNVT_temp_p
M
Display indoor temperature
12
nvoApplicMode
SNVT_hvac_mode
O
Display operating mode
13
nvoSetpoint
SNVT_temp_p
O
Display desire temperature
14
nvoOnOff
SNVT_switch
O
Display ON/OFF status
15
nvoFanStatus
SNVT_switch
O
Display fan speed
16
nvoERVMode
SNVT_count
O
Display ERV operating mode
17
nvoErrorCode
SNVT_count
O
Display Error code
18
nvoDeviceAlarm
SNVT_state
O
Remote control lock, Filter sign, Thermo ON/OFF,
Error occurrence status display
19
nvoOccOpMode
SNVT_switch
O
Cooling only/Heating only setup status display
20
nvoCoolTempLock
SNVT_switch
O
Display low temperature limit setting status
21
nvoHeatTempLock
SNVT_switch
O
Display high temperature limit setting status
22
nvoUserLockout
SNVT_switch
O
Display the restriction of remote control use
23
nvoEnergyConp
SNVT_elec_kwh_l
O
%JTQMBZFMFDUSJDJUZVTBHF 5JNF1FSJPE
24
nvoEnergyCon
SNVT_elec_kwh_l
O
Display electricity usage (Basic date)
25
nvoRuntimep
SNVT_time_hour
O
%JTQMBZVTFEIPVST 1FSJPE
26
nvoRuntime
SNVT_time_hour
O
Display used hours (Basic date)
27
nvoDevListDesc
SNVT_str_asc
O
Indoor unit HW information
No.
Name
Type
M/O
Description
1
nviDigitalOut[6]
SNVT_ switch
O
Control Digital output of DMS
2
nviAllOff
SNVT_hvac_emerg
O
Control all indoor unit / ERV OFF
3
nvoDigitalOut[6]
SNVT_ switch
O
Display Digital output status of DMS
4
nvoDigitalIn[8]
SNVT_ switch
O
Display Digital input status of DMS
5
nvoSystemLock
SNVT_ switch
O
Display System Lock status of DMS
6
nvoDMS2Alarm
SNVT_ count
O
Display communication error of the sub device
connected to DMS
7
nvoSystemAlarm
SNVT_ count
O
Display error satus
No.
Name
Type
M/O
Description
1
nciSndHrtBt
SNVT_time_sec
4$15NBY4FOE5JNF
O
Send Heartbeat
2
nciMinOutTm
SNVT_time_sec
4$15NJO4FOE5JNF
O
Minimum Send Time
3
nciMinDeltaTemp
SNVT_temp_p
4$15NJO%FMUB5FNQ
O
Min. difference before update
4
nciDelayStatrup
SNVT_time_sec
4$15QXSVQ%FMBZ
O
Delay time after a power-up
(2) DVM system object
(3) Configuration properties