2. ERV interface module
MIM-N10
1) Features
CN4
CN3
RED
CN2
BLK
YE
L
RED Y-GRN
t
Communication interface module between new communication ERV and controller
t
Connect 1 ERV interface module to Max. 16 ERVs
t
Individual control – Maximum 16 ERVs
t
Group control – Maximum 16 groups
t
Supported communication type
1) Conventional communication ERV
↔
New communication upper level controller
2) New communication ERV
↔
Conventional communication upper level controller
3) New communication ERV
↔
New communication upper level controller
❋
This interface module does not support connection between Conventional communication
ERV
↔
Conventional communication upper level controller
CN4
CN3
RED
CN2
BLK
YE
L
RED Y-GRN
59.4
96.1
(Unit : mm)
2) Product specification
Power Supply
DC12V
Power Consumption
2.4 W
Operating Temperature range
-10°C~50°C
Operating Humidity range
10%RH~90%RH
Communication
RS485 x 2
Maximum Communication Length
1000M
Maximum number of connection
1) New communication ERV
↔
Conventional communication upper level controller
''&37&37T
R1/R2 : 1 upper level controller
2) Conventional communication ERV
↔
New communication upper level controller
''&37&37T
335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4#"$OFU(8-POXPSLT(8
connection is allowed)
3) New communication ERV
↔
New communication upper level controller
''&37&37T
335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4#"$OFU(8-POXPSLT(8
connection is allowed)