Do not run Tracking except for the following conditions:
After initial installation.
- After initial installation, run Tracking for DMS to recognize the installation structure.
- Make sure actual system air conditioner information matches the Tracking
information displayed on DMS.
- When the actual system air conditioner information does not match the Tracking
information on DMS, check the installation.
Changes in installation
- After additional installation of the unit, if Tracking has not been performed, DMS
cannot recognize the additional units and the controlling, monitoring and power
distribution to the unit will not be available.
- After removing of the unit, if Tracking has not been performed, DMS may distribute
power to the removed unit and the error on power distribution result may occur.
Make sure actual system air conditioner information matches the Tracking
information displayed on DMS.
- When the actual system air conditioner information does not match the Tracking
information on DMS, check the installation.
- When the actual information does not match the Tracking information on DMS,
power distribution result error may occur, and abnormal Peak power management
may lead to Peak occurrence.
- If you do not know whether information matches or not, do not run Tracking.
Run Tracking when there are no communication errors between each devices and the DMS.
- Device with communication error will not be recognized on DMS therefore,
monitoring, controlling and power distribution cannot be done.
- If Tracking has been run and there are communication error between centralized
controller and the transmitter, you cannot bring information on the indoor units
connected to the Transmitter.
- If Tracking has been run and there are communication error between centralized
controller and the DMS, you cannot bring information on the indoor units connected
to the Centralized controller.
Do not run Tracking when the outdoor unit circuit breaker switch is off.
- If Tracking has been run when the outdoor unit circuit breaker switch is off, DMS can
not recognize the outdoor unit.
- Since DMS cannot recognize the outdoor unit, all the indoor units connected to this
outdoor unit can not be recognized as well and therefore controlling, monitoring
and the power distribution is not available.
Do not run Tracking when the Centralized controller is off.
- If Tracking has been run when the outdoor Centralized controller is off, DMS can not
recognize the centralized controller.
- Since DMS cannot recognize the Centralized controller, all the indoor units connected
to this centralized controller can not be recognized as well and therefore controlling,
monitoring and the power distribution is not available.
CAUTION
Using the DMS through the Web (Continued)