E-
27
ENGLISH
Using the DMS through the Web (Continued)
2
Check the indoor/outdoor units connected to the watt-hour
meter.
3
Check the SIM transmitter channel (watt-hour meter).
If the indoor unit power is supplied from the outdoor unit,
set the ‘Outdoor SIM ch.’ only.
( ‘Outdoor SIM ch.’ signifies the watt-hour meter connected
to the outdoor unit.)
If the indoor unit power is supplied separately, set both
‘Outdoor SIM ch.’ and the ‘Indoor SIM ch.’.
( ‘Indoor SIM ch.’ signifies the watt-hour meter connected to
the indoor unit.)
4
Set the indoor units that the power will be distributed.
If you do not set up the indoor unit information, result of
the power distribution will displayed as 0.
5
Press ‘Save’.
Changed power distribution setting will be saved on DMS.
Caution
Information of the watt-hour meter, connected to the
indoor unit, should be correct. If the watt-hour meter
information is incorrect when you set up the indoor
unit channel, error may occur on result of the power
distribution.
If you wish to distribute power on certain indoor unit,
you must set the SIM channel. If you do not set the
SIM channel, power will not be distributed and result
of the power distribution will be 0.
Consult installer if any information change occurs
on the watt-hour meter with indoor/outdoor unit
connection.