background image

E-

24

Using the DMS through the Web (Continued)

Function Explanation

  Users can set, inquire, and edit the information of power  

distribution section.  

  Refer to pg. 4 for more information on the Power Distribution 

Function.

Setting and Viewing the Power Distribution Function

Using the power Distribution Function

1

If clicking the ‘Edit’ button from the 

, area 

 is activated 

and users can set the desired section. Select one of possible  
settings which are 1 section, 2 sections, and 3 sections.

2

As shown in the above picture, only Section A is existed.  
It is from 00:00 to 24:00.

MIM-D00_IB_E_29777-2.indd   24

2009-05-08   ソタタ・10:08:11

Summary of Contents for MIM-D00

Page 1: ...USER SMANUAL MIM D00 DMS Data Management Server DB98 29777A 4 E K C CHINESE ENGLISH ...

Page 2: ...the DMS Do not spill water into the DMS Do not operate the DMS with wet hands Do not install the DMS in a location where it will come into contact with the combustible gases machine oil sulphide gas etc Do not press buttons with a pointed thing Do not pull or bend the DMS cable excessively Do not use this DMS for other purpose Do not spray an insecticide or other combustible things on the DMS Do n...

Page 3: ...NG THE WEB ENVIRONMENT 10 USING THE DMSTHROUGH THE WEB 10 Login 11 Monitoring and Control 12 Monitoring and Control ERV System 16 View Error History 20 Set Run andView Schedule 21 SettingandViewingthePowerDistributionFunction 24 SettingandViewingthePowerDistributionEnvironment 26 Inquire Power Distribution Result 29 Viewing Power Distribution Result 31 Setting the Indoor Unit Restriction 33 Settin...

Page 4: ...net Control Web The DMS has a built in web server function and can be accessed from a remote location to operate status monitoring control error history and schedule setting of the system air conditioners Using an Upper Level Controller When a separate upper level controller S NET series is used a number of DMS can be controlled with one central management system Data Storage The DMS has its own d...

Page 5: ...ce that controls 16 groups of the DVM air conditioner A central control device of a DVM system which is located between a DMS and an outdoor unit transmitter TRANSMITTER A data transmitter of a DVM system which is located between a central controller and an outdoor unit SIM The Abbreviation of Signal input Module A device that transmits power usage of an outdoor unit by being inputted it from a wa...

Page 6: ...level controller When an error is occurred inform the error details to an e mail saved on DMS Interface with Upper Level Controller The DMS receives control data from the upper level controller and sends the received data to the lower level system The upper level controllers of the DMS are the S NET series and the connectible S NET series are S NET 3 S NET i and S NET mini S NET 3 is a program tha...

Page 7: ...e of remote controllers Both the On time and the Off time can not be set at the same time and only one must be set Weekly Repeat Maximum 10 events per day Daily Repeat Maximum 70 events Each schedule can be used selectively by using the run schedule stop schedule order At most 256 schedules can be set The indoor units can be controlled by the schedule function of the DMS in at least 1 min interval...

Page 8: ... days worth of data After 93 days the oldest data is deleted and the latest data is saved This data can be viewed through the built in Web page of the DMS or by S NET 3 In order to use the power distribution function in the DMS relevant devices as shown above must be installed Consult the installers Save Integrated Power Distribution Data System Architecture S NET 3 Centralized Controller SIM Watt...

Page 9: ...view the distributed power on each section DMS will always show the result of the power distribution on section 1 regardless of section 2 or 3 For 2 sections 24 hours can be divided as follow 00 00 08 30 17 30 24 00 Time Division A Time Division B Time Division A Time Segmentation If communication error occurs between DMS and the lower level controllers actual power usage and the result of power d...

Page 10: ...RE is installed automatically if the PC is connected to the Internet and when the DMS is accessed for the first time JRE can also be downloaded from http java sun com j2se Install Internet Explorer 6 0 or later version IE6 0 or later version must be installed on the PC Please install IE6 0 or later version through Windows Update Using the DMS through the Web Access Method In order to access the DM...

Page 11: ...s pressed after typing in the ID and the password the ID and password fields are cleared 5 The default DMS user setting as follow ID admin PASS 1234 Change the ID and the password for security reasons Refer to 3 2 11 for user management Login admin Menu Organization If Login is successful the following menu appears Click on the menu to move to the corresponding page Monitoring and Control Viewing ...

Page 12: ...indoor unit But if the ERV system is installed can check the whole ERV control status Monitoring and Control Monitoring and Control 1 The status of all indoor units can be viewed from the Monitor all indoor units The color of the squares represents the following meaning and the name of each indoor unit is displayed inside of squares Gray Blue Green Red ...

Page 13: ...and buttons next to the desired temperature Temperature unit of the DMS will be set on either Celsius or Fahrenheit depending on the temperature unit used by the indoor unit Mode Set The current mode of the selected indoor unit is displayed in light blue Click on the desired mode to change modes When controlling the operation mode indoor unit will be controlled in the last controlled value of the ...

Page 14: ...elect All Clear all The simultaneous control of whole installed indoor units is possible If you want to control all the indoor units press the button on the indoor unit control screen If ERV system is connected and is selected with indoor units only the power ON OFF and the control are possible for the ERV In order to select the indoor unit only if the indoor unit is installed by mixing with the E...

Page 15: ...nsult the installer to use the emergency stop function Refer to the installation manual for explanation about the emergency stop 7 Communication Error Display When a communication error between the DMS and the lower controller is occurred a message as below is displayed as red Communication error Please check the error history menu for error reference During the normal operation it is not displaye...

Page 16: ...on status of all ERVs and control each ERV Monitoring and Control ERV System Monitoring and Control 1 The status of all ERVs can be viewed from the Monitor all indoor units The color of the squares represents the following meaning and the name of each ERV is displayed inside of squares Gray Blue Green Red ...

Page 17: ...he selected ERV Only when an error is occurred it is displayed as red During the normal operation it is not displayed on the screen Power Click on this button to turn on and turn off the selected ERV Mode Set The current mode of the selected ERV is displayed in light blue Click on the desired mode to change modes When controlling the ERV operation mode DMS saves the last value of each operation mo...

Page 18: ...hen pressing the button can use the wired remote control in each room Default 4 Select All Clear all The simultaneous control of whole installed ERV s is possible If you want to control all the ERV units press the button on the ERV control screen If indoor unit is connected and is selected with ERV only the power ON OFF and the control are possible for the indoor unit The indoor unit will run in t...

Page 19: ...onitored but not controlled The emergency stop function can only be used when the external contact control of the DMS is used Consult the installer to use the emergency stop function Refer to the installation manual for explanation about the emergency stop 7 Communication Error Display When a communication error between the DMS and the lower controller is occurred a message as below is displayed a...

Page 20: ...r History page 2 The error history can be viewed according to date Select the date in the list box and press the Search button to view the error history according to the selected period 3 The error history includes the device name address time when error occurred time when error was fixed error code error contents and status solve unsolved 4 Select and delete errors by selecting the check boxes in...

Page 21: ...chedule button in to create a new schedule Refer to Adding a Schedule 3 Press the Edit button in after selecting a schedule in to edit a set schedule Refer to Adding a Schedule 4 Press the Delete button in after selecting a schedule in to delete the selected schedule 5 Press the Run schedule button in after selecting a schedule in to run the selected schedule 6 Press the Stop schedule button in af...

Page 22: ...etting the remote control operated as below ON Allow the Remote Control Use Can use the wired wireless remote control and the indoor unit button in each room OFF Disallow the Remote Control Use Cannot use the wired wireless remote control and the indoor unit button in each room LEVEL1 a When turning ON by the centralized controller or DMS Allow the remote control use b When turning OFF by the cent...

Page 23: ...k box from the the selected event is deleted 6 When pressing the Save button from the after setting all schedule information the schedule information is saved to the DMS 7 When pressing the Cancel button from the turn back to the schedule list screen Note If you do not set the end date the schedule does not have period limit and the end date will not appear on the screen Temperature unit of the DM...

Page 24: ...n on the Power Distribution Function SettingandViewingthePowerDistributionFunction Using the power Distribution Function 1 If clicking the Edit button from the area is activated and users can set the desired section Select one of possible settings which are 1 section 2 sections and 3 sections 2 As shown in the above picture only Section A is existed It is from 00 00 to 24 00 ...

Page 25: ... Section A and Section B are existed in 2 Sections Can inquire and set the border time between Section A and Section B When pressing the Save button from the after editing the border time from the area set time is adopted If the border time between Section A and Section B is 08 00 Section A is 00 00 08 00 and Section B starts from 08 01 ...

Page 26: ...ion Environment 1 Check the address and the channel on the SIM transmitter that is connected to the watt hour meter SIM Transmitter with the address 0 7 will be displayed as 16 23 on DMS when tracking Channel information of the terminal with SIM transmitter and the watt hour meter connections displayed as follows Terminal block on the very left of the SIM transmitter is Terminal block 1 Terminal b...

Page 27: ...ibuted If you do not set up the indoor unit information result of the power distribution will displayed as 0 5 Press Save Changed power distribution setting will be saved on DMS Caution Information of the watt hour meter connected to the indoor unit should be correct If the watt hour meter information is incorrect when you set up the indoor unit channel error may occur on result of the power distr...

Page 28: ...DMS user can set up the Virtual channel In order to execute power distribution value from the watt hour meter should be manually inspected Virtual channel should be set on each watt hour meter Watt hour meter setting If CT watt hour meter is used click Watt hour meter Setting to set the CT proportion for each watt hour meter SIM transmitter should be installed to use this setting You may click Ind...

Page 29: ... all the indoor units 2 Select whether to check the power consumption or the rate for all indoor units by period in Total power consumption can be checked only when the watt hour meters are connected If not only the consumption ratio can be checked 3 Select the time period to check in Only data of the maximum of 93 days is saved on DMS 4 Press Calculation in to display the result 5 Press Save As F...

Page 30: ...check in If the DMS is set to group mode and one group has more than two indoor units each individual indoor unit will be checked 3 Select watt hour or Running in Power consumption or running time per date of the selected indoor unit 4 Select the time period to check in 5 Press Search in to display the result 6 Press Save As File to save the result in MS Excel file format It is recommended to save...

Page 31: ...stribution Result 1 Click SETUP FOR POWER DISTRIBUTION on the DMS web page 2 When the Virtual channel for the Indoor Outdoor unit is set above screen will appear 3 Select the time period and click calculation to display the result ...

Page 32: ...to check the result of power distribution in rate If you use virtual channel you cannot check the power usage for individual day You may check the individual indoor unit s daily operation time regardless of the channel type or settings Caution Due to rounding up the value there could be slight difference to the actual power usage Using the DMS through theWeb Continued ...

Page 33: ...estrict the indoor unit as cool only or heat only Setting the Indoor Unit Restriction Setting the Indoor Unit Restriction 1 Click RESTRICTED INDOOR UNIT USE on the DMS web page 2 Click Edit on the restricted indoor unit use screen Edit will change to Save ...

Page 34: ...n mode will be automatically set to operate in pre set control mode You can set the different control mode to each of the indoor units Cool only indoor unit Users can select between fan and cool mode Heat only indoor unit Users can select between fan and heat mode Ex When the cool only indoor unit with the control mode set to fan mode is changed to heat mode DMS will perceive it and control the in...

Page 35: ... temperature You can set the lower limit temperature between 18 C 65 F and 30 C 86 F 6 Set upper limit temperature Heat You can set the upper limit temperature by selecting Cancel or Apply If the desired temperature is higher than the upper limit temperature when indoor unit is operating in heat mode DMS controls the desired temperature in the upper limit temperature You can set the upper limit te...

Page 36: ...ntroller is MIM A202 and is in group mode If the centralized controller is in group mode and the transmitter is MIM B13 or MIM B04A Except above situations DMS changes the control mode limit of all indoor units under the same outdoor unit to same control mode limit If the centralized controller is in group mode and is above MIM M202A and all the transmitters under the centralized controller are ab...

Page 37: ...DMS users can set and view information related to the DMS system installation and operation The installer must complete the system environment setup when installing the DMS Setting andViewing the System Environment System environment setup ...

Page 38: ...to be modified if possible The schedule function and the power distribution function may be affected by changing the time 3 Change Password For the safety passwords exchange between the DMS and the upper controller S NET Series At this time users can change passwords of devices that are connected to the DMS 4 Priority If a DMS is connected with several upper controllers users set to allow a settin...

Page 39: ...ess by pressing the Test button after pressing the Apply When the delivery It is set to Cancel CAUTION When changing the password of the relevant site account e mail address must change the DMS The SMTP server is a mail server of an Internet portal site that a user registered Ask the correct name of the mail server to the relevant Internet company 7 DMS name Setup You can manage more conveniently ...

Page 40: ...Running LED Edit will change to Save 3 Select the mode you wish to set DMS status indicates whether or not DMS operates normally Green light will flicker every 5 seconds when DMS operates normally Running status of indoor unit DO1 Solid green light will turn on if there is at least one indoor unit operating DMS will output signal to DO1 4 Click Save Changed setting will be saved ...

Page 41: ...story Setting history will be saved in following categories Tracking Power distribution setting Power distribution environment setting and Time setting If you want to check Power distribution setting be aware that you can only check the latest saved setting if there were number of changes made within a day Function Explanation You can view the history of all the settings Log ...

Page 42: ...us use with care User can order the Retry of aTracking and manage the name of devices on theTracking information screen Information may be lost if Tracking is executed Consult the installer if possible when executing Tracking Tracking 1 Press Tracking Group mode or Tracking Room mode Group mode Tracking by searching the indoor unit RMC address Room mode Tracking by searching the indoor unit Main a...

Page 43: ...E 43 ENGLISH 2 When the Tracking Password Input window appears enter the password 3 When the Tracking Confirm window appears press Confirm Tracking will start ...

Page 44: ...racking fails re start the tracking Edit button will change to Save button Following window will appear when there are indoor units not using the centralized control If you have selected Tracking Room mode indoor unit RMC address will be displayed If there are MIM A202A and MIM B13A transmitters connected to the DMS outdoor unit information on tracking result will show as below 09 00 transmitter 1...

Page 45: ...E 45 ENGLISH 6 Enter the name of the centralized controller and the indoor units 7 Press Save Changed name of the centralized controller and the indoor unit will be saved on DMS ...

Page 46: ...akoccurrence Ifyoudonotknowwhetherinformationmatchesornot donotrunTracking RunTrackingwhentherearenocommunicationerrorsbetweeneachdevicesandtheDMS DevicewithcommunicationerrorwillnotberecognizedonDMStherefore monitoring controllingandpowerdistributioncannotbedone IfTrackinghasbeenrunandtherearecommunicationerrorbetweencentralized controllerandthetransmitter youcannotbringinformationontheindoorunit...

Page 47: ...r user ID Password and Description ID should be 4 10 letters long starting with a alphabet and can be used with numbers 3 Click Add There are no limits on number of users Entered user information will be saved on DMS Note DMS manager should change the ID and the password for security and maintenance Adding New User ...

Page 48: ...rs select the user you wish to edit You can select number of users at once or select individual user 3 Edit the Password and the Description on selected ID ID cannot be edited 4 Click Edit Edited user information will be saved on DMS Using the DMS through theWeb Continued Editing User ...

Page 49: ... DMS web page 2 When User Management screen appears select the user you wish to delete You can select number of users at once or select individual user 3 Click Delete If confirmation window appears click OK to delete selected user Deleting User ...

Page 50: ... 8 pam 0 72 procps 2 0 14 dhcpcd ifupdown 0 6 4 LGPL software glibc 2 3 2 util linux 2 11h The software used in this product is developed from Apache Software Foundation http www apache org This product includes software developed by the Indiana University Extreme Lab For further information please visit http www extreme indiana edu This product uses the cryptographic software developed by Eric Yo...

Page 51: ...uest samsung com Berkeley DB software db 3 2 9 Refer to APPENDIX for original text of licence 1 GPL2 0 2 LGPL2 1 3 ApacheLicense1 1 4 Enhydra Public License 1 1 5 dom4j license 6 ISC license 7 jaxen license 8 ncurses license 9 pullparser2 license 10 OracleBerkleyDBLicense 11 libxml2License 12 pam license 13 OpenSSL Combined License 14 tcp wrapper license 15 BSD license 16 pure ftpd license 17 Open...

Page 52: ......

Reviews: