47
Drain pipe and drain hose installation
1.
Unscrew the 4 tapped screws to remove the cover of the drain hose
connection port.
Drain hose connection
port
2.
Insert the flexible hose to the drain hose port.
NOTE
t
Fix the flexible hose to the indoor unit wiht the supplied
cable clamp securely.
(Use the screwdriver to fix the flexible hose securely.)
Cable clamp
3.
Install the drain hose so that its length can be as short as possible.
Internal diameter of the drain hose should be the same or slightly
bigger than the external diameter of the drain hose port.
t
Inner diameter of the drain hose
32mm(Inner diameter)
NOTE
t
Install the drain hose with a slope away from the unit to
give adequate drainage of condensate.
t
Fix the flexible hose to the PVC with the supplied cable tie
securely.
Indoor Unit
Clamp
Insulation cover drain
Insulation drain hose
Cable-tie
t
Must fit tightly against
body without any gap.
CAUTION
No gap
4.
Wrap the drain hose with the insulation drain as shown in figure and
secure it.
ENGLISH