The example of ERV PLUS option setting method
1.
Press
Set
and
ESC
buttons at the same time for more than 3 seconds.
t
(Main menu) will be displayed and then press the [ ]/[ ] button to select no.6.
2.
Press [
>
] button to select the number you will set.
t
Press [ ]/[ ] button and select no.1
3.
Press [
>
] button to enter the data setting stage.
t
When you enter the setting stage, the current setting value will be displayed.
1 2 3 4
Data bit
Data1: Nonuse of cold breeze prevention
Data2: Cold breeze prevention: Non use of humidification when the heating THERM is off
Data3: No operation for air supply fan of defrosting operation
Data4: Nonuse of humidification in heating operation
Example of data setting stage display
4.
Press [
<
]/[
>
] button to select the desired Data1.
t
Press [<]/[>] button to select no.1.
t
The wired remote controller option is changed from “Nonuse of cold breeze
prevention” to “Use of cold breeze prevention”.
5.
Press
Set
button to complete the option setting.
t
Save the setting value and exit to sub menu.
6.
Press
Esc
button to exit to normal mode.