74
Wired Remote Controller Installation/Service Mode
Additional Functions of Your Wired Remote Controller
NOTE
t
‘NONE’ will be displayed if the indoor unit does not support the function.
In some cases, the setting may not possible or it may be not applied though it is set on the unit.
t
If communication initialization is needed after the setting, the system will reset automatically and
communication will be initialized.
Main
menu
Sub
menu
Function
Data bit
Factory
setting
Description
Unit
1
1
Wireless remote
controller Option
setting/checking (1)
Cooling/Heating selection
1
0
0 – Cooling/Heating,
1 – Cooling only
-
Use of wireless remote controller
2
1
0 – No use, 1 - Use
-
MAIN/SUB wired remote
controller
3
0
0 –MAIN, 1- SUB
-
Temperature unit
4
0
0 – Celcius(°C),
1 – Fahrenheit(°F)
-
2
Wireless remote
controller Option
setting/checking (2)
Temperature sensor selection
1
0
0 – Indoor unit,
1 – Wired remote controller
-
Use of average temperature
2
0
0 – No use, 1 - Use
-
Use of Auto mode
3
1
0 – No use, 1 - Use
-
Temperature display
4
0
0 – Set temperature,
1 - Room temperature
-
AC On/Off button function
5
0
0 – Indoor unit + ERV,
1 – Indoor unit only,
2 – ERV only,
-
3
Blade
setting/checking
Lock of Blade1
1
0
0 – Unlock, 1 – lock
-
Lock of Blade2
2
0
0 – Unlock, 1 – lock
-
Lock of Blade3
3
0
0 – Unlock, 1 – lock
-
Lock of Blade4
4
0
0 – Unlock, 1 – lock
-
4
ERV option
Setting/checking
Use of By-Pass mode
1
0
0 – No use, 1 - Use
-
Use of Auto mode
2
0
0 – No use, 1 - Use
-
Use of air purification mode
3
0
0 – No use, 1 - Use
-
Use of external control
4
0
0 – No use, 1 - Use
-
5
Room Temperature
compensation
Temperature control reference
1,2,3
0
-9 ~ 40°C(15~104°F)
0.1°C
Temperature compensation value
4,5,6
0
-9.9 ~ 9.9°C
0.1°C
6
Number of connected
units
Number of indoor units
1,2
-
0 ~ 16
-
Number of ERVs
3,4
-
0 ~ 16
-
7
Temperature increment/decrement (°C only)
1
0
0-1°C, 1-0.5°C, 2-0.1°C
-
8
Set/Check ERV Energy
saving operation
Select individual Energy saving
operation
1
0
0-ON/OFF alternating
operation,
1-Outdoor air cooling
operation for different
temperature setting
-
Minimum temperature of
outdoor air cooling
3,4
15
5 ~ 15°C (41~59°F)
°C
0
Factory option setting
1
0
0 – Unchanged
1 – Factory setting
-
2
1
Software code
1~6
-
Software code
-
2
Software version
1~6
-
Software version
-