62
Setting an indoor unit address and installation option
Setting an indoor unit installation option (suitable for the condition of each installation location)
1.
The receiver module of a wireless remote controller is at PBA phase.
(This receiver module is only for setting the option , not for operating the ERV+.)
You can set or check the MAIN installation option with the main menu 4 and sub menu 4 of a wired remote
controller.
2.
Set the installation option according to the installation condition of an air conditioner.
t
The default setting of an indoor unit installation option is “020010-100000-200000-300000”’ and “ 050000-
100000-200000-300000”.
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
External room
temperature sensor
/ Minimizing fan
operation when
thermostat is off
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
Hot water heater
-
EEV Step when
heating stops
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control output
/ External heater On or
Off signal
S-Plasma ion
Buzzer
Number of hours using
filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation /
Removing condensated
water in heating mode
EEV Step of stopped
unit during oil return/
defrost mode
Motion detect sensor
-
t
When setting the option other than above SEG values, the option will be set as “0”.
t
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option
additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
t
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
F4
F3
F1
F2
V2
V1
1(L) 2(N)
2
1
HOT
COIL
AC
POWER
OUTDOOR
COMMUNICATION
Wire Remote
Controller
DC 12 V
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)
COM1 COM2
(+) L
N
(-)
t
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)