60
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
-
-
-
-
-
Water tank sensor setting
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication
Details
Indication Details Indication
Details
3
0
-
0
-
0
-
0
-
0
Default (Direct
connected water
tank sensor)
1
Shared sensing
value of water
tank
1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place .
For example, When the indoor unit is installed 40 m (131 .2 ft) higher than the indoor unit installed at the lowest place,
select the option "1" .
2) Distance : The difference between the pipe length of the indoor unit installed at the farthest place from an outdoor unit and the pipe length
of the corresponding indoor unit from an outdoor unit .
For example, when the farthest pipe length is 100m and the corresponding indoor unit is 40m away from an outdoor unit, select
the option "2" . 100 m (328 .1 ft) – 40 m (131 .2 ft) = 60 m (196 .9 ft)
Changing a particular option
You can change each digit of set option .
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
The option mode
you want to
change
The tens’ digit of an
option SEG you will
change
The unit digit of an
option SEG you will
change
The changed value
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
D
Option
mode
0~F
Tens’
digit of
SEG
0~9
Unit digit
of SEG
0~9
The
changed
value
0~9
• When changing a digit of an indoor unit address setting option, set the SEG3 as ‘A’ .
• When changing a digit of indoor unit installation option, set the SEG3 as ‘2’ .
Ex) When setting the ‘buzzer control’ into disuse status.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
The option
mode you
want to
change
The tens’ digit
of an option
SEG you will
change
The unit digit
of an option
SEG you will
change
The changed
value
Indication
0
D
2
1
7
1
NOTE
Setting an indoor unit address and installation option
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 60
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 60
2023-06-15 오전 10:37:38