57
ENGLISH
Setting an indoor unit installation option (suitable for the condition of each installation location)
1 . Check whether power is supplied or not .
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit .
2 . The panel(display) should be connected to an indoor unit to receive option .
3 . Set the installation option according to the installation condition of a product .
- The default setting of an indoor unit installation option is “020000-100000-200010-300000
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit .
4 . Set the indoor unit option by wireless remote controller .
■
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
-
Central control
-
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
-
-
-
Opening the
electronic
expansion valve
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output
-
-
-
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
Heating setting
compensation
EEV opening of
an indoor unit
stopped during oil
return or Defrost
operation .
-
-
f
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as “indoor 1” .
f
SEG5 option for centralized control usage is set to 0(disuse) as a default setting . You must adjust the setting for this option
separately when centralized control needs to be used .
■
02 series installation option(Detailed)
Option No . : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
-
-
Use of central
control
-
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication
Details
Indication Details Indication Details Indication Details
0
2
0
-
0
-
0
Disuse
0
-
1
Use