67
ENGLISH
f
K4 input display order
(1) Current frequency
(2) Low pressure value
(3) Outdoor temperature
(4) Discharge temperature
(5) OLP
temperature
(6) COND temperature
(7) Suction temperature
(8) High pressure value
(9)
(10)
(11) MAIN
EEV
(12) Present running current
(13) Number of connected
hydro
units
(14) Number of operating
hydro
units
(15) Sum of hydro unit capacity
K4(Press and hold to
enter the setting)
K4
press(Number of press)
Displayed content
Display on segment
0 time
Main Micom version
Version (ex . 0912)
1 time
Inverter Micom version
Version (ex . 0912)
2 times
EEPROM version
Version (ex . 0912)
3 times
Automatically assigned address of the
units
SEG1
SEG2
SEG3, 4
Hydro unit: “A”
Hydro unit: “0”
Address (ex: 05)
4 times
Manually assigned address of the units
SEG1
SEG2
SEG3, 4
Hydro unit: “M”
Hydro unit: “A”
Address (ex: nU)
[K4] Number of press
Displayed contents
Display
SEG1
SEG2
SEG3
SEG4
1
Current frequency
1
15Hz
015
2
Low pressure value
2
1 .56 MPa (226 .3 psi)
156
3
Outdoor temperature
3
23 .5 °C (74 .3 °F)
235
4
Discharge temperature
4
80 .7 °C (177 .3 °F)
807
5
OLP temperature
5
95 °C (203 °F)
950
6
COND temperature
6
26 .3 °C (79 .3 °F)
263
7
Suction temperature
7
26 .7 °C (80 .1 °F)
267
8
High pressure value
8
1 .56 MPa (226 .3 psi)
156
9
9
10
A
11
MAIN EEV
B
1500Step
150
12
Present running current
C
15A
150
13
Number of connected hydro units
D
10
010
14
Number of operating hydro units
E
10
010
15
Sum of hydro unit capacity
F
12000kcal/h
120