27
ENGLISH
f
AM048CNBFCB / AM072CNBFCB
Pr
essur
e dr
op fr
om hea
t
ex
changer (psi)
0.0
0.15
0.29
0.44
0.58
0.73
0.87
1.02
1.16
3.2
4.0
5.3
6.6
7.9
9.2
Water flow rate (GPM)
Connecting strainer
f
Use a strainer with 50 mesh (Diameter of each hole must be under 0 .4 mm (0 .016 inch), excluding punching plate)
f
Connect the strainer after checking the direction of the strainer on the water inlet hole as shown in the illustration .
f
Wind the Teflon tape more than 15 times on the thread of the water pipe before connecting it .
f
Service port must face downward and angle should be within 45° on the left and the right side .
f
After installing the strainer, makes sure that there is no water leakage on the connection part .
f
For normal operation of the product, clean the strainer regularly (more than once a year) .
<Side view>
<Front view>
Strainer
45°
Water inlet pipe
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 27
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 27
2023-06-15 오전 10:37:26