Refrigerant pipe welding and safety information
Important information for refrigerant pipe work
f
Make sure there is no moisture inside the pipe .
f
Make sure there are no foreign substances and impurities in the pipe .
f
Make sure there is no leakage .
f
Make sure to follow the instruction when welding or storing the pipe .
Nitrogen flushing while brazing (DVM Hydro unit)
f
When brazing the refrigerant pipes, flush them with nitrogen gas as shown in the picture .
f
If you do not perform nitrogen flushing when brazing the pipes, oxide may form inside the pipe and can cause damage
to the important parts such as compressor and valves etc .
f
Adjust the flow rate of the nitrogen flushing with a pressure regulator to maintain 0 .05 m
3
/h (1 .77 ft
3
/h) or less .
f
When brazing the pipes on the connection port, cover the valve with wet cloth before brazing (to protect the parts within
the valve)
Brazed part
Nitrogen
Copper pipe [Φ6 .35 (1/4")]
Stop valve
Taping
High pressure hose
Nitrogen
Wet cloth
Gas side (brazed)
Flowmeter
Φ 6 .35 (1/4")
Pressure regulator
Direction of the pipe when brazing
f
Direction of the pipe should be headed downward or sideways when brazing .
f
Avoid brazing the pipe with pipe direction heading upward .
Downward
Side
Upward