7
ENGLISH
Preparing the installation
Tools required for installation
General tools
①
Vacuum pump
②
Torque wrench
③
Pipe cutter
④
Reamer
⑤
Pipe bender
⑥
Leveling tool
⑦
Screw driver
⑧
Spanner
⑨
Drill
⑩
L wrench
⑪
Measuring tape
Tools for operation
①
Thermometer
②
Resistance meter
③
Electroscope
Accessories (supplied)
Before the installation, make sure to check if following accessories are included inside the DVM Hydro unit / Hydro unit HT .
Installation manual
Drain plug
Drain cap
Additional accessory (not included)
Additional accessory needs to be purchased separately and installed to operate DVM Hydro unit / Hydro unit HT .
Wired remote
controller
MWR-WW10UN
f
Recommended specification of the strainer
Model type
Model name
Work pressure
Work
temperature
Water pipe
connection part
Mesh size
Material
(Strainer/Mesh)
HE
AM036CNBDCH
1 .0 MPa (145 psi)
-20 ~ 35 °C
(-4 ~ 95 °F)
NPT 1” (25A)
50 Mesh
AISI316/SUS304
AM048CNBDCH
AM096CNBDCH
AM144CNBDCH
NPT 1-1/4” (32A)
HT
AM048CNBFCB
-20 ~ 43 °C
(-4 ~ 109 .4 °F)
NPT 1” (25A)
AM072CNBFCB
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 7
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 7
2023-06-15 오전 10:37:22
2023-06-15 오전 10:37:22