AC 208 ~ 230 V or AC 24V thermostat
f
Connect the indoor thermostat to B19~B26 of the PBA terminal block .
f
Connect a thermostat to the designated terminal as stated in the rated table .
f
Only 1 type of thermostat can be connected . (B19~B22 or B23~B26)
f
Product will not operate when signal for cooling and heating mode is inputted at the same time .
V1
V2
L
N
AC 208 ~ 230 V Thermostat
AC 24 V Thermostat
• Maximum allowable current of each terminal is below 10mA
CAUTION
Specification table
Part
Specification
Terminal block (AC 208 ~ 230 V)
B19: Output power L (for cooling mode)
B20: Input power N (for cooling mode)
B21: Output power L (for heating mode)
B22: Input power N (for heating mode)
Terminal block (AC 24V)
B23: Output power L (for cooling mode)
B24: Input power N (for cooling mode)
B25: Output power L (for heating mode)
B26: Input power N (for heating mode)
Connection type
Connect to indoor power controller
Input (B19~B22)
AC 208 ~ 230 V (Maximum 10 mA)
Input (B23~B26)
AC 24 V (Maximum 10 mA)
Condition for operation
When B20 or B24 is detected -> cooing mode
When B22 or B26 is detected -> heating mode