Safety precautions
CAUTION SIGNS
After completing the installation, run the trial operation . If no error occurs, explain to the customer how to use and clean the
product according to the user’s manual . In addition give the installation manual and the user’s manual to the customer .
Before the installation, check if the product is in good shape .
f
Do not install the product with the damage which occurred during shipment .
All of the materials used to manufacture product and packages are eco-friendly and they are recyclable .
Refrigerant used in this product must be added or disposed in an appropriate way by qualified personnel .
f
At the end of the life cycle, take it to a proper recycling or disposal center or return it to the dealer so that it can be
disposed correctly .
Combination rate
f
This product should be connected to DVM S / DVM S2 / DVM water outdoor units .
f
Installation combinations:
- This product should be among 50~130% of the outdoor unit's nominal capacity .
- When this product is connected to heat pump outdoor units at 130~180% combination rate, it must meet the
conditions below .
1) Combination rate for indoor units: Standard indoor units (ex: cassette, duct, etc .) under 100% + Hydro Unit/Hydro
Unit HT under 80% .
2) Standard indoor units (ex: cassette, duct, etc .) should be operated in cooling mode only and DVM Hydro unit/ Hydro
Unit HT should be operated in heating mode only (including floor heating) .
3) It is not possible to operate standard indoor units (ex: cassette, duct, etc .) and DVM Hydro unit/ Hydro unit HT at the
same time .
- When combining an outdoor unit with an indoor unit, refer to the tables below for the capacity of DVM Hydro HT .
Capacity correction
AM048CNBF
✴✴
48 kBTU/h
AM072CNBF
✴✴
72 kBTU/h