Dead remote controller but red lights are on the indoor PCB
On first startup you will notice two red LEDs light up, after around 4 minutes the screen will light up.
If the controller hasn’t started after around 4 minutes and the control board has the red LEDs lit up, there is a small brown eeprom PCB plugged into the
board. You will need to check that this is plugged in fully, if this is missing then this is the problem and you will need a new brown PCB.
00 shows on the remote controller
00 will show when the MIM board is first powered up, this means that the PCB has activated but the outdoor unit is not connected and fault code E201 will
appear.
Check the F1 & F2 wiring is good between the outdoor unit and indoor unit, also check the power to the outdoor unit.
01 shows on the remote controller
01 on the controller means that there is power to the controller but the outdoor unit isn’t connected to the control board.
Check the F1 & F2 wiring is ok between the outdoor and indoor unit and make sure the outdoor unit has power.