Piping instal

lation

Piping installation

About the piping work

Water connections must be made in accordance with the Water 

Piping and Wiring diagram delivered with the unit, respecting the 

water inlet and outlet. If air, moisture or dust gets in the water 

circuit, problems may occur. Therefore, always take into account 

the following when connecting the water circuit:
•  Use clean pipes only.
•  Hold the pipe end downwards when removing burrs.
•  Cover the pipe end when inserting it through a wall so that no 

dust and dirt enter.

•  Use a good thread sealant for the sealing of the connections.
•  The sealing must be able to withstand the pressures and 

temperatures of the system. When using non-brass metallic 

piping, make sure to insulate both materials from each other 

to prevent galvanic corrosion.

•  Because brass is a soft material, use appropriate tooling for 

connecting the water circuit. Inappropriate tooling will cause 

damage to the pipes.

  CAUTION

•  Be careful not to deform the unit piping by using excessive 

force when connecting the piping. Deformation of the piping 

can cause the unit to malfunction.

•  Always use two wrenches (spanners) for tightening or 

loosening the water connections, and tighten connections 

with a torque wrench as specified in the below table. If not, 

connections and parts can be damaged and leak.

•  The unit is only to be used in a closed water system. If 

applications are in open water circuit, it will generate heat 

exchangers fouling, corrosion, and leak.

Name

Tightening torque

BSPP1

350~380 kgf•cm

34~37 N•m

Connecting the water pipes

Connecting the water piping typically follows the below procedure:

Connect the water piping to the outdoor unit.

Connect the water piping to the indoor unit.

Connect the recirculation piping.

Connect the drain hose to the drain.

Fill the water circuit.

Fill the DHW tank.

Insulate the water piping.

  NOTE

•  Do not use excessive force when connecting the piping. 

Deformation of the piping can cause malfunctioning of the 

unit.

•  Connect the shut-off valve (with integrated filter) to the 

outdoor unit water inlet, using the thread sealant. At this time, 

the filter should be directed downward so that impurities can 

be collected.

•  Connect the field piping to the shut-off valve.
•  Connect the shut-off valve to the outdoor unit water outlet, 

using the thread sealant.

Water 

Outlet

Shut Off Valve (1) IN (inc. Filter) / 
Shut Off Valve (1) OUT

Water 

Inlet

  NOTE

•  About the shut-off valve with integrated filter:

 

– The installation of the shut-off valve at the water inlet is 

mandatory.

 

– Mind the flow direction of the valve.

Water Charging

Fill water into the outdoor unit by opening the shut-off and drain 

valves.

Water outlet

Water inlet

Piping installation

Summary of Contents for AE CXYD Series

Page 1: ...WaterHeatPump Installation manual EHS Mono Outdoor Unit AE CXYD Thank you for purchasing this Samsung product Before operating this unit please read this manual carefully and retain it for future refe...

Page 2: ...14 Connecting the water pipes 14 Water Charging 14 Setting capacity and pre pressure of the expansion vessel 15 Protection of the water circuit freezing 15 Outdoorwater piping insulation 17 Minimum a...

Page 3: ...uman health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users s...

Page 4: ...unit Neversit orstand on the product All the materials used forthe manufacturing and packaging of the airto waterheat pump are recyclable The packing material and exhausted batteries of the remote con...

Page 5: ...ng flammable refrigerants Safety checks are required to minimize the ignition risk for servicing the units containing flammable refrigerants Servicing shall be performed following the controlled proce...

Page 6: ...the recovery units orcylinders If compressors orcompressoroils are to be removed make sure that they have been evacuated to the acceptable level to ensure that flammable refrigerant does not remain in...

Page 7: ...product in the protective packaging and keep covered until final installation Preparation of both horizontal and vertical transport routes and equipment might be required in orderto get the product i...

Page 8: ...d does not generate any unnecessary noise and vibration Position the outdoorunit so that the airflows directly towards the open area Place the outdoorunit where there are no plants and animals because...

Page 9: ...d laterto violate the protection rules Unit mm 1 000 1 000 1 000 500 1 000 500 500 500 300 1 000 500 1 000 1 000 500 When installed on the ground When installed in a place with a flat roof When instal...

Page 10: ...and serviceable undersafe working conditions forpeople orthings Installing the unit at a locationwith strong winds Outdoorunit must be fixed firmly so that it can withstand the wind speed of the stro...

Page 11: ...lean it with waterto remove attached salinity 6 If the protective coating orgalvanised steel of the product is damaged during the installation ormaintenance make sure to repairit 7 Check the condition...

Page 12: ...tions Woodenpallet Forklift 1 050mm NOTE When looking at the product from the front there is a centerof gravity right from the middle of the product Referto the centerof gravity mark attached to the p...

Page 13: ...runs away correctly and safely 150mm WARNING If the drainage is not adequate it can lead to stagnant water and ice build up causing system performance issues and possible damages Drainhole 20 Drainpl...

Page 14: ...ench as specified in the below table If not connections and parts can be damaged and leak The unit is only to be used in a closed watersystem If applications are in open watercircuit it will generate...

Page 15: ...the installation the installation height is considered 0m When Expansion vessel has a capacity 8 liters and1bar pre charged Watervolume of total system forreliable performance is minimum 30 Liter AE0...

Page 16: ...raturevalue When using the EHS forcooling in the summertime an anti freeze valvewith ambient sensoris required to avoid unwanted opening due to lowwatertemperatures To protect the field piping against...

Page 17: ...m Minimum insulation thickness mm 20 19 20 30 32 30 40 40 40 50 50 NOTE This recommendation ensures good operation of the unit however local regulations may differand shall be followed Minimum activew...

Page 18: ...ct the earth wire to the gas pipe water pipe lighting rod ortelephone wire If earthing is not complete electric shock orfire may occur Install the circuit breaker Failing to install a circuit breaking...

Page 19: ...t and route them through the factory mounted cable sleeves into the switch box Powerand communication cable configuration Powersupply cable must be guided through the knock out hole on the bottom righ...

Page 20: ...itchwithinyourarm s reach that disconnects all poles with contact gap of a least 3 mm Route the cable through the frame Connect the wires to the terminal block and fix the cable with the cable tie R S...

Page 21: ...the selected options press and hold the K2 switch for2 seconds to store the value The changed value of the option will be saved when the entire segment display blinks and tracking mode begins CAUTION...

Page 22: ...K 2 BLANK 1 3 times InverterFault Detection Comp 1 K 3 I 1 4 times End Key operation K2 Numberof Press KEY operation 7 segment display 1 time Trial operation in Cooling mode K 4 BLANK BLANK 2 times Di...

Page 23: ...nd on this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field Unit kg tCO e a b DO NOTCHARGE Refrigerant type GWPvalue R 290 3 GWP Global Warmi...

Page 24: ...e Error Detect when the system is not operated OUTDOOR UNIT E440 Forbid Heat mode Operation when OutdoorTemperature is over43 C OUTDOOR UNIT E441 Forbid Cooling Mode when Outdoor Temperature is Low10...

Page 25: ...T_CT Thermistor CompressorTop T_D Thermistor Discharge pipe T_EI Thermistor EVI In T_EO Thermistor EVI Out T_II Thermistor Heat ExchangerIn T_S Thermistor Suction pipe T_WI Thermistor WaterIn T_WO The...

Page 26: ...HE Part Description CV Check Valve COMP Compressor HX_IC Heat Exchanger Intercooler HX_M Heat Exchanger Main Outdoorunit HX_PHE Heat Exchanger PHE IPMC IPM Cooler OFM OutdoorFan Motor AC Accumulator P...

Page 27: ...with the higher set temperature to Zone 2 d A ir vent included in tank integrated hydro unit In case that the water piping would be located in a higher position than the air vent of the tank integrate...

Page 28: ...essel Decoupler Safety group Safetyvalve Manometer Expansion vessel 3waymixingvalveforfloorheating incaseofcombinationwithradiators Mixing valve temperature sensorb Vibro isolating mounting bases Symb...

Page 29: ......

Page 30: ...This appliance is filledwith R 290 A3...

Reviews: