Installation guide at the seashore

Make sure to follow the below guides when installing at the 

seashore.

Do not install the product in a place where it is directly 

exposed to sea water and sea breeze.
•  Make sure to install the product behind a structure (such as 

a building) that can block sea breeze.

Sea

Sea breeze

Outdoor 

unit

Sea

Sea

Sea breeze

Sea breeze

Protection wall

Outdoor 

unit

Outdoor 

unit

•  A protection wall should be constructed with a solid 

material that can block the sea breeze and the height and 

width of the wall should be 1.5 times larger than the size 

of the outdoor unit. (Please secure more than 700 mm of 

space between the protection wall and the outdoor unit for 

air circulation.)

Consider that the salt particles clinging to the external panels 

should be sufficiently washed off
•  When a product is installed at the seashore, periodically 

clean it with fresh water to remove attached salt deposits.

Make sure that the base of the unit is installed at water level 

and therefore has optimum drainage. Because trapped water 

at the bottom of the outdoor unit significantly promotes 

corrosion.
•  Prevent blockage of the drain hole by foreign substances, 

by cleaning adequately.

•  Make sure to clean the base plate adequately and regularly 

as dirt, sand and other substances stay moist and promote 

corrosion.

If the product is installed within 500 m of a seashore, special 

anticorrosion treatment (like special coating) is required.
•  Please contact your local Samsung representative for 

further details.

When the product is installed at a seashore, periodically clean 

it with water to remove attached salinity.

If the (protective) coating or galvanised steel of the product is 

damaged during the installation or maintenance, make sure 

to repair it.

Check the condition of the product periodically.
•  Check the installation site every 3 months and perform 

anticorrosion treatment.

Selecting a location in cold climates

  NOTE

•  When operating the unit in a low outdoor ambient 

temperature, be sure to follow the instructions described 

below.

In heavy snowfall areas it is very important to select an installation 

location where the snow will not affect the unit. If lateral snowfall 

is possible, make sure that the heat exchanger coil is not affected 

by the snow. (If necessary construct a lateral canopy)

 Snow-proof hood

 Frame

Estimated snow fall

Ground

Construct a large canopy.

Construct a pedestal.
•  Install the unit high enough off the ground to prevent it 

from being buried under snow.

Heavy snow fall area

If the product is installed in a region of heavy snow, allow enough 

distance between the product and the ground (or piled up snow).
•  In areas with heavy snow fall, piled snow could block the 

air intake. To avoid this, install a frame that is higher than 

estimated snow fall. In addition, install a snow-proof hood to 

avoid snow from piling on the outdoor unit.

•  If ice accumulates on the base, it may cause critical damage 

to the product. (e.g., a lakeside in a cold area, the seashore, an 

alpine region, etc.)

•  In a heavy snowfall area, do not install the drain plug and 

drain cap in the outdoor unit. And, it may cause frozen ground. 

Therefore, take appropriate measures to prevent it.

•  Make a space more than 150 mm between the bottom of the 

outdoor unit and the ground for installation.

•  Make sure that the product is located at least 150 mm above 

the maximum expected level of snow.

150 mm

Summary of Contents for AE CXYD Series

Page 1: ...WaterHeatPump Installation manual EHS Mono Outdoor Unit AE CXYD Thank you for purchasing this Samsung product Before operating this unit please read this manual carefully and retain it for future refe...

Page 2: ...14 Connecting the water pipes 14 Water Charging 14 Setting capacity and pre pressure of the expansion vessel 15 Protection of the water circuit freezing 15 Outdoorwater piping insulation 17 Minimum a...

Page 3: ...uman health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users s...

Page 4: ...unit Neversit orstand on the product All the materials used forthe manufacturing and packaging of the airto waterheat pump are recyclable The packing material and exhausted batteries of the remote con...

Page 5: ...ng flammable refrigerants Safety checks are required to minimize the ignition risk for servicing the units containing flammable refrigerants Servicing shall be performed following the controlled proce...

Page 6: ...the recovery units orcylinders If compressors orcompressoroils are to be removed make sure that they have been evacuated to the acceptable level to ensure that flammable refrigerant does not remain in...

Page 7: ...product in the protective packaging and keep covered until final installation Preparation of both horizontal and vertical transport routes and equipment might be required in orderto get the product i...

Page 8: ...d does not generate any unnecessary noise and vibration Position the outdoorunit so that the airflows directly towards the open area Place the outdoorunit where there are no plants and animals because...

Page 9: ...d laterto violate the protection rules Unit mm 1 000 1 000 1 000 500 1 000 500 500 500 300 1 000 500 1 000 1 000 500 When installed on the ground When installed in a place with a flat roof When instal...

Page 10: ...and serviceable undersafe working conditions forpeople orthings Installing the unit at a locationwith strong winds Outdoorunit must be fixed firmly so that it can withstand the wind speed of the stro...

Page 11: ...lean it with waterto remove attached salinity 6 If the protective coating orgalvanised steel of the product is damaged during the installation ormaintenance make sure to repairit 7 Check the condition...

Page 12: ...tions Woodenpallet Forklift 1 050mm NOTE When looking at the product from the front there is a centerof gravity right from the middle of the product Referto the centerof gravity mark attached to the p...

Page 13: ...runs away correctly and safely 150mm WARNING If the drainage is not adequate it can lead to stagnant water and ice build up causing system performance issues and possible damages Drainhole 20 Drainpl...

Page 14: ...ench as specified in the below table If not connections and parts can be damaged and leak The unit is only to be used in a closed watersystem If applications are in open watercircuit it will generate...

Page 15: ...the installation the installation height is considered 0m When Expansion vessel has a capacity 8 liters and1bar pre charged Watervolume of total system forreliable performance is minimum 30 Liter AE0...

Page 16: ...raturevalue When using the EHS forcooling in the summertime an anti freeze valvewith ambient sensoris required to avoid unwanted opening due to lowwatertemperatures To protect the field piping against...

Page 17: ...m Minimum insulation thickness mm 20 19 20 30 32 30 40 40 40 50 50 NOTE This recommendation ensures good operation of the unit however local regulations may differand shall be followed Minimum activew...

Page 18: ...ct the earth wire to the gas pipe water pipe lighting rod ortelephone wire If earthing is not complete electric shock orfire may occur Install the circuit breaker Failing to install a circuit breaking...

Page 19: ...t and route them through the factory mounted cable sleeves into the switch box Powerand communication cable configuration Powersupply cable must be guided through the knock out hole on the bottom righ...

Page 20: ...itchwithinyourarm s reach that disconnects all poles with contact gap of a least 3 mm Route the cable through the frame Connect the wires to the terminal block and fix the cable with the cable tie R S...

Page 21: ...the selected options press and hold the K2 switch for2 seconds to store the value The changed value of the option will be saved when the entire segment display blinks and tracking mode begins CAUTION...

Page 22: ...K 2 BLANK 1 3 times InverterFault Detection Comp 1 K 3 I 1 4 times End Key operation K2 Numberof Press KEY operation 7 segment display 1 time Trial operation in Cooling mode K 4 BLANK BLANK 2 times Di...

Page 23: ...nd on this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field Unit kg tCO e a b DO NOTCHARGE Refrigerant type GWPvalue R 290 3 GWP Global Warmi...

Page 24: ...e Error Detect when the system is not operated OUTDOOR UNIT E440 Forbid Heat mode Operation when OutdoorTemperature is over43 C OUTDOOR UNIT E441 Forbid Cooling Mode when Outdoor Temperature is Low10...

Page 25: ...T_CT Thermistor CompressorTop T_D Thermistor Discharge pipe T_EI Thermistor EVI In T_EO Thermistor EVI Out T_II Thermistor Heat ExchangerIn T_S Thermistor Suction pipe T_WI Thermistor WaterIn T_WO The...

Page 26: ...HE Part Description CV Check Valve COMP Compressor HX_IC Heat Exchanger Intercooler HX_M Heat Exchanger Main Outdoorunit HX_PHE Heat Exchanger PHE IPMC IPM Cooler OFM OutdoorFan Motor AC Accumulator P...

Page 27: ...with the higher set temperature to Zone 2 d A ir vent included in tank integrated hydro unit In case that the water piping would be located in a higher position than the air vent of the tank integrate...

Page 28: ...essel Decoupler Safety group Safetyvalve Manometer Expansion vessel 3waymixingvalveforfloorheating incaseofcombinationwithradiators Mixing valve temperature sensorb Vibro isolating mounting bases Symb...

Page 29: ......

Page 30: ...This appliance is filledwith R 290 A3...

Reviews: