Note:
The set point in the heat exchanger circuit which is valid at the end of the charging cy-
cle will be used again at the beginning of the next cycle.
If times-of-use have been set for DHW heating, the
DHW temperature set point
adjusted at
the rotary switch is applied during these times-of-use. Outside the times-of-use, the
Sustained
DHW temperature
is used. This does not apply when a storage tank thermostat is used.
Time-controlled switchover of storage tank sensors
By configuring a second storage tank sensor SF2 over the function block CO4 -> F19 -1, it is
possible to determine that the storage tank sensor SF1 is used for day mode in the DHW cir-
cuit and that the storage tank sensor SF2 is used for night mode. As a result, different stor-
age tank volumes can be kept at a constant temperature according to a time schedule, and
also at different temperatures if the
DHW set point
and
Sustained DHW temperature
differ
from one another.
Stop storage tank charging
The controller stops charging the storage tank when the water temperature measured at sen-
sor SF2 has reached the temperature T =
DHW temperature
+
hysteresis
. To do so, the heat
exchanger charging pump is switched off first.
When there is no heating operation or when the flow temperature demand in the system is
lower, the corresponding valve is closed. The storage tank charging pump is switched off af-
ter t =
Lag time of storage tank charging pump
x
valve transit time
.
Functions
WE
Configuration
Storage tank sensor SF1
1
CO4 -> F01 - 1
Storage tank sensor SF2
1
CO4 -> F02 - 1
Flow sensor VF4
0
CO4 -> F05
Time-controlled switchover of storage tank
sensors
0
CO4 -> F19
Parameters
WE
Rotary switch / Range of values
DHW temperature set point or charging
temperature set point with CO4 -> F01 - 0
55 °C
Bottom /Min. to max. DHW temperature
Sustained DHW temperature
40 °C
Bottom /Min. to max. DHW temperature
Parameters
WE
Parameter level / Range of values
Min. DHW temperature*
40 °C
PA4 / 5 to 90 °C
EB 5579 EN
87
Functions of the DHW circuit