Note:
The controller ID is indicated in the extended operating level under Info 2 (first value in
the sequence).
When Modbus is activated and, at the same time, the dial-up in case of error is released, the
connection with the building control station is established first, and then the text message is
sent. If the first attempt to connect to the building control station fails, the controller tries
again until the programmed number of redialing attempts has been exhausted.
In Germany, the access numbers (tAPnr) of the SMS service center are currently:
4
D1
network: 0171 252 1002 (alternatively, 0171 252 1099 is also possible)
4
E-Plus
network: 0177 1167
4
Cellnet
(UK) network: 0044 0786 098 0480 - routing into the
D1
,
D2
and
E-Plus
net-
works.
Add “0” to the number when dialing from a telephone extension. The mobile phone number
(HAndy) must be entered as follows: 49 xxx yyyyyy, where xxx stands for 160, 171 or any
other valid dialing code and yyyyyy represents the specific phone number of the mobile you
wish the error message to be sent to.
Functions
WE
Configuration
Text message
0
CO6 -> F08 - 1
Modem function
0
CO6 -> F03 - 1
Automatic modem configuration
0
CO6 -> F04 - 1
Parameters
*
WE
Parameter level / Range of values
Modem dialing pause (P)
5 min
PA6 / 0 to 255 min
Modem time-out (t)
5 min
PA6 / 1 to 255 min
No. of redialing attempts (C)
15
PA6 / 1 to 255
Access number (tAPnr)
–
PA6 / Max. 22 characters; 1, 2, 3, …, 9, 0;
“-“ end of a string; “P“ pause
Mobile phone number (HAndy)
–
PA6 / Max. 22 characters; 1, 2, 3, …, 9, 0;
“-“ end of a string; “P“ pause
* –> section 9.3 (Description of communication parameter settings)