Setting the times-of-use
Three times-of-use can be set for each day of the week.
If only one time-of-use is required, the start and stop times of the second time-of-use must be
set to identical times. In this case, the third time-of-use is not displayed.
If only two times-of-use are required, the start and stop times of the third time-of-use must be
set to identical times.
The times-of-use for the different control circuits are set at the rotary switches
one after the
other
:
Times-of-use
Rotary switch
Position
Heating circuit 1*
Top
Heating circuit 2*
Middle
DHW heating/heating circuit 3*
Bottom
Circulation pump
Bottom
* Refer to page 161 for assignment
Parameters
WE*
Range of values
Period/day
1–7
1–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Start first time-of-use
6:00
0:00 to 24:00h; in steps of 15 minutes
Stop first time-of-use
22:00 0:00 to 24:00h; in steps of 15 minutes
Start second time-of-use
22:15 0:00 to 24:00h; in steps of 15 minutes
Stop second time-of-use
22:15 0:00 to 24:00h; in steps of 15 minutes
Start third time-of-use
–
0:00 to 24:00h; in steps of 15 minutes
Stop third time-of-use
–
0:00 to 24:00h; in steps of 15 minutes
* Default values (WE) valid for heating circuit 1/primary heat exchanger circuit (top rotary switch)