1.9
Setting room and DHW temperature set points
For the heating circuits, the required room temperatures during the day (
Day set point
) and
during the night (
Night set point
) can be set.
In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
The temperature set points for the different control circuits are set at the rotary switches
one
after the other
:
Desired temperature set point
Switch
Position
Heating circuit 1*: Day set point
Top
Heating circuit 1*: Night set point
Top
Heating circuit 2*: Day set point
Middle
Heating circuit 2*: Night set point
Middle
DHW heating*: DHW temperature set point
Bottom
Heating circuit 3*: Day set point
DHW heating*: DHW temperature sustained value
Bottom
Heating circuit 3*: Night set point
* Refer to page 161 for assignment
Parameters
WE
Rotary switch / Range of values
Day set point
20 °C Top, middle / 0 to 40 °C
Night set point
15 °C Top, middle / 0 to 40 °C
DHW temperature set point
55 °C Bottom / Min. to max. DHW temperature
Proceed as follows:
Turn appropriate rotary switch to “Set point temperature“.
Display shows: temperature
q
Set temperature value.
Return the rotary switch to the required operating mode (left side).
20
EB 5579 EN