Function
WE
Configuration
Room sensor RF1, 2, 3
0
CO1, 2, 3 -> F01 - 0
Exceptions:
CO1 -> F01 - 1 and CO7 -> F03-1
CO1 -> F01 - 1 and CO7 -> F04-1
CO1 -> F01 - 1 and CO7 -> F05-1
7.15 Feeder pump operation
In systems Anl 3.0, 5.0, 7.x and 12.x, the feeder pump UP1 only starts to operate in the de-
fault setting when a flow temperature demand of a secondary controller exists.
If CO7 -> F14 - 1 is configured, this is also the case when the controller’s own secondary
circuit requires heat.
Function
WE
Configuration
UP1 operation to cover own demand
0
CO5 -> F14 - 1
7.16 Locking manual level
To protect the heating system, this function can be used to lock the manual level. When this
function has been activated, automatic mode is started when the rotary switch is set to
.
Functions
WE
Configuration
Locking manual levels
0
CO5 -> F21 - 1
7.17 Locking the rotary switches
When this function has been activated, the controller remains in automatic mode regardless
of the rotary switch positions. The rotary switches can no longer be used to adjust the con-
troller settings.
Functions
WE
Configuration
Locking the rotary switches
0
CO5 -> F22 - 1
7.18 Setting a customized key number
To avoid the unauthorized modification of functions and parameters of the controller, the de-
fault key number can be replaced with an individual key number.
Choose your custom key number between 0100 and 1900.
EB 5579 EN
111
System-wide functions