5.1.2 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points each for the
Outdoor temperature
, the
Flow temperature,
the
Reduced
flow temperature
and the
Return flow temperature
. The
Max. flow temperature
and
Min. flow
temperature
parameters mark the upper and lower limits of the flow temperature.
Note:
The
Day set point
and
Night set point
parameters are no longer available when the
4-point characteristic has been selected, provided no additional functions (e.g.
Optimiza-
tion
,
Flash adaptation
) have been selected.
Function
WE
Configuration
4-point characteristic
0
CO1, 2, 3 -> F11 - 1
Parameters
WE
Parameter level / Range of values
Outdoor temperature
Point 1
Point 2
Point 3
Point 4
–15 °C
–5 °C
5 °C
15 °C
PA1, 2, 3 / –30 to 50 °C
Flow temperature
Point 1
Point 2
Point 3
Point 4
70 °C
55 °C
40 °C
25 °C
PA1, 2, 3 / 5 to 130 °C
72
EB 5579 EN
Functions of the heating circuit
t
VLmax
t
VLmin
t
VL
100
90
80
70
60
50
40
30
20
10
[°C]
20
15
10
5
0
–5
–10 –15 –20
P1
P2
P3
P4
[°C]
t
A
Fig. 6 · 4-point characteristic
P1 to P4
Points 1 to 4
tVL
Flow temperature
tA
Outdoor temperature
... min
Min. tVL
...max
Max. tVL
4-point characteristic
Reduced 4-point characteristic