Sensor calibration is to be activated in CO5 via function block F20.
An incorrect sensor calibration can be deleted by setting F20 - 0.
Proceed as follows:
Switch to configuration and parameter level. Display shows:
0 0 0 0
q
Set valid key number.
Confirm key number. Display shows:
PA1
q
Select configuration level CO5.
Open configuration level CO5.
q
Select function block F20.
Activate editing mode for function block F20.
q
Select appropriate sensor icon:
Room sensor RF, heating circuits 1, 2, 3
Outdoor sensor AF, heating circuits 1, 2, 3
Flow sensor VF, heating circuits 1, 2, 3
Flow sensor VF1, primary heat exchanger circuit
Flow sensor VF2, DHW circuit
Solar collector sensor VF3
Return flow sensor RüF
Storage tank sensor SF1
Storage tank sensor SF2
Storage tank sensor SF3
Flow sensor VF4
Display measured value.
Measured value blinks.
26
EB 5579 EN
Start-up