Functions
WE
Configuration
Device bus
0
CO7 -> F01 - 1; device bus address
TROVIS 5570 Room Panel in Rk1
0
CO7 -> F03 - 1; device bus address
TROVIS 5570 Room Panel in Rk2
0
CO7 -> F04 - 1; device bus address
TROVIS 5570 Room Panel in Rk3
0
CO7 -> F05 - 1; device bus address
Note:
The room panel can only be supplied by the controller when no meter bus plug-in
module is installed.
7.12.6 Display error messages issued by the device bus
The setting CO7 -> F16 - 1 causes the controller to react to the error messages from the de-
vice bus by generating the “Err 5” error message as long as the faults of the other device bus
participants exist. If, additionally, the setting CO5 -> F07 - 1 is configured, the fault alarm
output BA13 is also set. The black squares under the corresponding numbers at the top of
the display indicate (with “Err 5”) which device bus address is defective for the first 23 de-
vice bus participants.
Regardless of the CO7 -> F16 setting, error messages received over device bus basically
lead to the control station (GLT) being dialed when the modem function is active. You can
EB 5579 EN
109
System-wide functions
12...26.5V AC/
15...36V DC
BA12
BA13
UP On/off
UP Speed
Pump management - COM
COM BA12, BA13
Y COM
TROVIS 5579
TROVIS 5570
Y1
Y2
0...10V
0...10V
Y3
0...10V
16
18
20
22
15
17
19
21
23
24
26
28
30
25
27
29
14
1
2
3
4
5
6
7
8
9
Fig. 12 · Connecting the TROVIS 5570 Room Panel to the controller