80 - 144
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P14.04
Communica tion
overtime fault
time
0.0 (invalid), 0.1~60.0 s
When the function code is set as 0.0, the communication
overtime parameter is invalid.
When the function code is set as non-zero, if the interval
time between two communications exceeds the
communication overtime, the system will report “RS485
communication faults” (CE).
Generally, set it as invalid; set the parameter in the continuous
communication to monitor the communication state.
0.0 s
○
P14.05
Transmission
fault processing
0:
Alarm and stop freely
1:
No alarm and continue to run
2:
No alarm and stop according to the stop means (only
under the communication control)
3:
No alarm and stop according to the stop means (under
all control modes)
0
○
P14.06
Communication
processing
action selection
0x00~0x11
LED ones
:
0: Operation with response
. The drive will respond to all
reading and writing commands of the upper monitor.
1: Operation without response.
The drive only responds to the
reading command other than the writing command of the drive.
The communication efficiency can be increased by this method.
LED tens:
0: Communication encrypting valid
1: Communication encrypting invalid
0x00
○
P17 Group Monitoring function
P17.00 Sett frequency
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
0.00 Hz
●
P17.01
Output
frequency
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
0.00 Hz
●
P17.02
Ramp reference
frequency
Display current ramp reference frequency of the inverter
Range: 0.00Hz~P00.03
0.00 Hz
●
P17.03 Output voltage
Display current output voltage of the inverter
Range: 0~1200 V
0 V
●
P17.04 Output current
Display current output current of the inverter
Range: 0.0~3000.0 A
0.0 A
●
P17.05
Motor speed
Display the rotation speed of the motor.
Range: 0~65535 RPM
0 RPM
●
P17.08
Motor power
Display current motor power
Range:-300~300% (the rated current of the motor)
0.0 %
●
P17.09
Output torque
Display the current output torque of the inverter.
Range: -250.0~250.0 %
0.0 %
●
P17.10
Motor frequency
evaluation
Evaluate the motor rotor frequency on open loop vector.
Range: 0.00Hz~ P00.03
0.00 Hz
●
P17.11 DC bus voltage Display current DC bus voltage of the inverter
0.0 V
●