Function Parameters
59
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P07 Group Human-Machine Interface
P07.00
User’s
password
0~65535
The password protection will be valid when setting any
non-zero number.
00000:
Clear the previous user’s password, and make the
password protection invalid.
After the user’s password becomes valid, if the password is
incorrect, users cannot enter the parameter menu. Only
correct password can make the user check or modify the
parameters. Please remember all users’ passwords.
Retreat editing state of the function codes and the password
protection will become valid in 1 minute. If the password is
available, press PRG/ESCto enter into the editing state of the
function codes, and then “0.0.0.0.0” will be displayed. Unless
input right password, the operator can not enter into it.
Note:
Restoring to the default value can clear the
password, please use it with caution.
0
○
P07.01
Parameter
copy
The function code determines the mode of parameters copy.
0:
No operation
1:
Upload
the local function parameter
to the keypad
2:
Download
the keypad function parameter
to the
inverter
(including all the motor parameters)
3:
Download
the keypad function parameter
to the
inverter (excluding the motor parameter of P02 group)
4:
Download
the keypad function parameters
to the
inverter (only for the motor parameter of P02 group)
Note:
After completing the 1~4 operation, the parameter
will come back to 0 automatically, the function of upload
and download excludes the factory parameters of P29.
0
◎
P07.02
QUICK/JOG
function
selection
0:
No function
1:
Jogging. Press QUICK/JOG to begin the jogging
running.
2:
Shift the display state by the shifting key. Press QUICK/JOG
to shift the displayed function code from right to left.
3:
Shift between forward rotations and reverse rotations.
Press QUICK/JOG to shift the direction of the frequency
commands. This function is only valid in the keypad
commands channels.
4:
Clear UP/DOWN settings. Press QUICK/JOG to clear
the set value of UP/DOWN.
5:
Coast to stop. Press QUICK/JOG to coast to stop.
6:
Shift the running commands source. Press QUICK/JOG
to shift the running commands source.
7:
Quick commission mode (committee according to the
non-factory parameter)
1
◎