Function Parameters
51
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.07
S7 terminal
function
selection
18:
Multi-step speed terminal 3
19:
Multi- step speed terminal 4
20:
Multi- step speed pause
21:
ACC/DEC time option 1
22:
ACC/DEC time option 2
23:
Simple PLC stop reset
24:
Simple PLC pause
25:
PID control pause
26:
Traverse Pause (stop at the current frequency)
27:
Traverse reset (return to the center frequency)
28:
Counter reset
29:
Torque control prohibition
30:
ACC/DEC prohibition
31:
Counter trigger
32:
Length reset
33:
Cancel the frequency change setting temporarily
34:
DC brake
36:
Shift the command to the keypad
37:
Shift the command to the terminals
38:
Shift the command to the communication
39:
Pre-exciting command
40:
Clear the power
41:
Keep the power
61:
PID pole switching
0
◎
P05.08
S8 terminal
function
selection
0
◎
P05.09
HDI terminal
function
selection
0
◎
P05.10
Polarity
selection of the
input terminals
The function code is used to set the polarity of the input
terminals.
Set the bit to 0: the input terminal is anode.
Set the bit to 1: the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
BIT5
BIT6
BIT7
BIT8
S6
S7
S8
HDI
Setting range: 0x000~0x1FF
0x000
○
P05.11 Switch filter time
Set the sample filter time of S1~S8 and HDI terminals. If the
interference is strong, increase the parameter to avoid the
disoperation.
0.000~1.000s
0.010 s
○
P05.12
Virtual terminals
setting
0x000~0x1FF (0: Disabled, 1:Enabled )
BIT0:
S1
virtual terminal
BIT1:
S2
virtual terminal
BIT2:
S3
virtual terminal
BIT3:
S4
virtual terminal
BIT4:
S5
virtual terminal
BIT5:
S6
virtual terminal
0x000
◎