Function Parameters
75
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P10.34
Simple PLC 0~7
stage ACC/DEC
time selection
Below is the detailed instruction:
Function
code
Binary bit Step
ACC/
DEC
0
ACC/
DEC
1
ACC/
DEC
2
ACC/
DEC
3
P10.34
BIT1
BIT0
0
00
01
10
11
BIT3
BIT2
1
00
01
10
11
BIT5
BIT4
2
00
01
10
11
BIT7
BIT6
3
00
01
10
11
BIT9
BIT8
4
00
01
10
11
BIT11 BIT10
5
00
01
10
11
BIT13 BIT12
6
00
01
10
11
BIT15 BIT14
7
00
01
10
11
P10.35
BIT1
BIT0
8
00
01
10
11
BIT3
BIT2
9
00
01
10
11
BIT5
BIT4
10
00
01
10
11
BIT7
BIT6
11
00
01
10
11
BIT9
BIT8
12
00
01
10
11
BIT11 BIT10
13
00
01
10
11
BIT13 BIT12
14
00
01
10
11
BIT15 BIT14
15
00
01
10
11
After the users select the corresponding ACC/DEC time,
the combined 16 binary bits will change into decimal bit,
and then set the corresponding function codes.
Setting range: 0x0000~0xFFFF
0x0000
○
P10.35
Simple PLC
8~15 stage
ACC/DEC time
selection
0x0000
○
P10.36
PLC restart
mode
0: Restart from the first stage
. Stop during running (cause by
the stop command, fault or power loss), run from the first stage
after restart.
1: Continue to run from the stop frequency
; stop during
running (cause by stop command or fault), the inverter will
record the running time automatically, enter into the stage after
restart and keep the remaining running at the setting frequency.
0
◎
P10.37
Multi-step time
unit selection
0: Seconds
; the running time of all stages is counted by second
1: Minutes
; the running time of all stages is counted by minutes
0
◎
P11 Group Protective parameters
P11.00
Phase loss
protection
0x000~0x111
LED ones:
0:
Input phase loss software protection disable
1:
Input phase loss software protection enable
LED tens:
0:
Output phase loss protection disable
1:
Output phase loss protection enable
LED hundreds:
0:
Input phase loss hardware protection disable
1:
Input phase loss hardware protection enable
111
○