118 - 144
Communication Protocol
Function instruction
Address
definition
Data meaning instruction
R/W
characteristics
2008H
The upper limit torque of braking
torque (0~3000), 1000
corresponds to the 100.0% of
the rated current of the motor
W/R
2009H
Special control command word
Bit0~1:=00:motor 1
=01:motor 2
=10:motor 3
Bit2:=1 torque control
=0:speed control
W/R
200AH
Virtual input terminal command ,
range: 0x000~0x1FF
W/R
200BH
Virtual input terminal command ,
range: 0x00~0x0F
W/R
200CH
Voltage setting value (special for
V/F separation)
(0~1000, 1000 corresponds to
the 100.0% of the rated voltage
of the motor)
W/R
200DH
AO output setting 1 (-1000~1000,
1000 corresponds to 100.0%)
W/R
200EH
AO output setting 2
(-1000~1000, 1000 corresponds
to 100.0%)
W/R
SW 1 of the inverter
2100H
0001H: forward running
R
0002H: forward running
0003H: stop
0004H: fault
0005H: POFF state
SW 2 of the inverter
2101H
Bit0: =0:bus voltage is not
established =1:bus voltage is
established
Bi1~2:=00:motor 1
=01:motor 2
=10:motor 3
Bit3 =0:asynchronous motor
Bit4:=0:pre-alarm without overload
=1:overload pre-alarm
Bit5~ Bit6:=00:keypad control
=01:terminal control
=10:communication
control
R
Fault code of the inverter
2102H
See the fault type instruction
R
Identifying code of the inverter
2103H
CV50 -----0x0107
R
Operation frequency
3000H
Range: 0.00Hz~P00.03
R