Function Parameters
61
-
144
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P07.07
The parameter
selection of the
stop state
0x0000~0xFFFF
BIT0
: set frequency
(Hz on, frequency flickering slowly)
BIT1
: bus voltage (V on)
BIT2
: input terminals state
BIT3
: output terminals state
BIT4
: PID reference (% flickering)
BIT5
: PID feedback value (% flickering)
BIT6
: reserved
BIT7
: analog AI1 value (V on). Inverters
≤
15kW can be set
by the digital potentiometer on the keypad and AI1 setting is
not available for the devices
≥
18.5kW.
BIT8
: analog AI2 value (V on)
BIT9
: analog AI3 value (V on)
BIT10
: high speed pulse HDI frequency
BIT11
: PLC and the current stage in multi-step speed
BIT12
: pulse counters
BIT13
: length value
BIT14
: upper limit frequency (Hz on)
0x00FF
○
P07.08
Frequency
display
coefficient
0.01~10.00
Displayed frequency=running frequency* P07.08
1.00
○
P07.09
Rotation speed
display
coefficient
0.1~999.9%
Mechanical rotation speed =120*displayed running
frequency×P07.09/motor pole pairs
100.0 %
○
P07.10
Linear speed
display
coefficient
0.1~999.9%
Linear speed= Mechanical rotation speed×P07.10
1.0 %
○
P07.11
Rectifier bridge
module
temperature
0~100.0
º
C
●
P07.12
Inverter module
temperature
0~100.0
º
C
●
P07.13 Software version 1.00~655.35
●
P07.14
Local
accumulative
running time
0~65535h
●
P07.15
High bit of power
consumption
Display the power used by the inverter.
The power consumption of the inverter =P07.15*1000+P07.16
Setting range of P07.15: 0~65535
kWh (*1000)
Setting range of P07.16: 0.0~999.9 kWh
●
P07.16
Low bit of power
consumption
●
P07.17
Load type
0: Constant Torque Load
1: Variable Torque Load
●
P07.18
Rated power of
the inverter
0.4~3000.0kW
●