Installation
RuggedRouter
®
RX1000 Family
15
RuggedCom
®
- Rev.122
3.2 Power Supply Wiring and Grounding
RX1000 and RX1100 support dual redundant universal high voltage range power
supplies: “Power Supply 1 (PS1)” and “Power Supply 2 (PS2)”. RX1000P and
RX1100P feature a universal high voltage range power supply as PS1, and a
separate 48VDC supply, PS2, to provide Power over Ethernet. The connections for
PS1, PS2 and the fail-safe relay are located on the terminal block as shown in Figure
7 and Figure 8.
Philips Screw Term inal w ithout C over
Philips Screw Term inal w ith C over
Safety C over
Safety C over
Screw s
C hassis G round
C onnection
Surge / C hassis
G round Jum per
Term inal
Figure 7: RX1000 Series Phillips Screw Terminal Block
Phoenix Plug Term inal w ithout C over
Phoenix Plug Term inal w ith C over
Safety C over
Screw s
Safety C over
C hassis G round
C onnection
Term inal
Surge / C hassis
G round Jum per
Figure 8: RX1000 Series Phoenix Plug Terminal Block
The RX1000 Family chassis ground connection, shown in Figure 9, uses a #6-32
screw. It is recommended to terminate the ground connection in a #6 ring lug, and to
use a torque setting not exceeding 15 in.lbs (1.7 Nm).