3/4 - 1.5 Hp 120V Single Phase (Wire for "Low Voltage")
To reduce the risk of
electric shock, the motor
is to be grounded per
local electrical code.
To reverse the motor Swap T5 and T8
T1
T3
T5
T4 T2
T8
L1 120VAC
Hot
L2 120VAC
Neutral
Incoming 1PH power
from control panel,
motor starter.
3/4 - 3 Hp 230V Single Phase (Wire for "High Voltage")
T5
T3
T2
To reduce the risk of
electric shock, the motor
is to be grounded per
local electrical code.
To reverse the motor Swap T5 and T8
T1
T4
T8
Incoming 1PH power
from control panel,
motor starter.
L1
L2
208 thru 240V Three Phase (Wire for "Low Voltage")
T1
T7
T2
T8
T3
T5
T4
T9
T6
To reduce the risk of
electric shock, the motor
is to be grounded per
local electrical code.
L1
Incoming 3PH power
from control panel,
motor starter, or VFD.
5 Hp 230V Single Phase (Wire for "High Voltage")
To reduce the risk of
electric shock, the motor
is to be grounded per
local electrical code.
T5
T4
T1
L2
L3
T8
L1
L2
Incoming 1PH power
from control panel,
motor starter.
To reverse the motor Swap T5 and T8
To reverse the motor Swap L1 and L2
440 thru 480V Three Phase (Wire for "High Voltage")
T1
T2
T4
T3
T7
T5
T8
T6
T9
L1
L2
L3
Incoming 3PH power
To reverse the motor Swap L1 and L2
from control panel,
motor starter, or VFD.
To reduce the risk of
electric shock, the motor
is to be grounded per
local electrical code.
41