Checking the Safety Circuit based on Positioning Unit
Procedure:
1. Using forced operation of Over limit switch for the external safety circuit of the
positioning unit, check to see if the Over limit input is being properly taken into
the positioning unit.
2. If necessary, input a program to start the JOG operation. Then operate the Over limit
input forcibly to check whether the motor will stop.
3. Using the JOG operation, check to see if the Over limit switch is functioning
properly.
Summary of Contents for NX-POSI1
Page 1: ...Catalog Number s NX70 POSIx NX POSIx NX70 700 Position User Manual ...
Page 6: ...6 ...
Page 14: ...14 ...
Page 22: ...22 ...
Page 38: ...38 ...
Page 64: ...64 ...
Page 79: ...79 Program ...
Page 82: ...82 Program ...
Page 106: ...106 Pulse output diagram ...
Page 107: ...107 Sample Program ...
Page 110: ...110 ...
Page 123: ...123 Action of the I O Flag Before and After a Home Return Operation Return Operation ...
Page 132: ...132 ...
Page 147: ...147 Pulse output diagram Deceleration stop operation In progress stop ...
Page 148: ...148 Forced stop operation Emergency stop Overrun ...
Page 158: ...158 ...
Page 170: ...170 ...
Page 178: ...178 Oriental Motor Co Ltd UPK W Series Open collector output stepping drive connection ...
Page 179: ...179 NX700 PLC External Dimensions 1 System Dimensions mm Motherboard Installation Diagram mm ...
Page 180: ...180 2 CPU I O Analog Unit Dimensions mm 3 Special Unit Dimensions mm ...
Page 183: ...183 Program ...
Page 187: ...187 Program ...
Page 188: ...188 ...
Page 194: ...Publication NX700 UM007A PositionA EN December 2010 ...
Page 195: ......
Page 196: ...Copyright 2010 RS Automation Co Ltd All rights reserved ...