Redefining Flow Control
status Alarm Menu
R1 enR - Relay 1 energised
R2 enR - Relay 2 energised
CR fLT - Critical fault
Critical Fault detected -Actuator disabled.
Loss of Feedback
EEPROM fault
nC fLT - non Critical fault
Non Critical fault detected- Actuator alarms active but
actuator remains functional. This may require intervention to
restore electrical operation.
Motor Stall
Torque/Thrust Overload
Loss of communications
Loss of Demand Signal
Over temperature
ee fLT - eepRoM parameters
EEPROM parameters out of range .
Actuator is disabled , restore defaults and check basic and
advanced parameters.
eC fLT - eepRoM fault Customer defaults
Customer defaults stored incorrectly or corrupted in the
EEPROM. Actuator runs. Cycle the power and restore the
customer defaults to remove the alarm.
ef fLT - eepRoM factory defaults
Actuator runs. Cycle power to remove the alarm. If problem
persists contact Rotork Process Controls.
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust or Torque
LOCREM
Local / Remote Control
MANJOG
Manual Jog
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CFG
Control Setup
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
BASIC
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
TORQ O
TORQ C
CL ACT
OP ACT
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
ASRACT
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
R1 enR
R2 enR
CR fLT
nC fLT
ee fLT
eC fLT
ef fLT
ovTeMp - over Temperature
Internal Temperature Sensor Tripped.
LosCoM - Loss of Remote bus Communications
Loss of serial bus communications greater than the COM TO
communications time out period has occurred.
LoCAL - Local Control selected
Actuator is selected for Local Operation. The actuator will
not respond to remote commands. Local operation must be
selected top modify parameters.
CL LIM - At Closed Limit
The actuator position is at or below the closed end of
travel limit.
o LIM - At open Limit
The actuator position is at or above the open end of
travel limit.
esd - emergency shutdown active
Emergency Shut Down command is active. The actuator will
not respond to any other commands until the ESD condition
is removed.
MonRLy - Monitor Relay Tripped
Monitor Relay tripped and actuator is not available for
remote control.
ovTeMp
LosCoM
LoCAL
CL LIM
o LIM
esd
MonRLy