A4
US
US
A4
US
A4
US
A4
10
hazardous Area Approvals
special Conditions for safe use (ATeX & IeCex approved actuators)
In accordance with clause 5.1 of IEC/EN 60079-1, the critical dimensions of the flamepaths are:
CML-100/250
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.145
13.5
Base/feedback shaft bush
-0.02
13.7
Feedback shaft bush/feedback shaft
0.06
13.7
Handknob shaft/lid
0.1
25.9
CMQ-250/500
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.235
29.8
Base/feedback shaft bush
-0.02
13.7
Feedback shaft bush/feedback shaft
0.06
13.7
Handknob shaft/lid
0.1
25.9
CMR-50/100/200
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.235
29.8
Base/output shaft
0.145
12.8
Handknob shaft/lid
0.1
25.9
CML-750
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.235
37.3
Base/feedback shaft bush
-0.02
13.7
Feedback shaft bush/feedback shaft
0.06
13.7
Handknob shaft/lid
0.1
25.9
CMQ-1000
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.235
37.3
Base/feedback shaft bush
-0.02
13.7
Feedback shaft bush/feedback shaft
0.06
13.7
Handknob shaft/lid
0.1
25.9
CMR-125/250
Flamepath
Maximum Gap (mm)
Maximum Width L (mm)
Lid/base
0.15
12.8
Base/pinion shaft
0.235
37.3
Base/ourtput shaft
0.145
13
Handknob shaft/lid
0.1
25.9
Note: Negative Sign denotes an interference fit.
wARnIng
The equipment utilises a non-metallic outer coating
and has a potential static hazard. Clean only with a
damp cloth.