Redefining Flow Control
basic setup
4. seT CLosed LIMIT of TRAveL
To set the Closed limit of travel for the actuator press the
DOWN button until CL LIM is displayed.
Press ENTER to put the actuator in to EDIT Mode. This will
allow parameter changes to be made.
Use the UP and DOWN buttons to move the actuator output
drive to the required CLOSED Position.
Press ENTER and the new CLOSED End of Travel Limit is saved
to the actuators memory.
The CLosed end of TRAveL LIMIT Is seT.
Press CANCEL to go back to top level menu.
STEP 1
SELECT LOCAL
OPERATION
STEP 2
SET OUTPUT
TORQUE/THRUST
STEP 4
SET CLOSE LIMIT
OF TRAVEL
STEP 5
SET OPEN LIMIT
OF TRAVEL
STEP 6
CALIBRATE COMMAND
SIGNAL ZERO SETPOINT
STEP 7
CALIBRATE COMMAND
SIGNAL SPAN SETPOINT
STEP 3
SELECT ACTION AT END
OF TRAVEL ( LIMIT OR FORCE)
STEP 8
DEADBAND
LOCAL
MANJOG
X
X
X
X
EDIT
LOCAL
CL L I M
LOCAL
EDIT
CL L I M
LOCAL
SAVED
EDIT
X
X
Fig. 35.4
Fig. 35.3
Fig. 35.2
Fig. 35.1