Redefining Flow Control
Installation & setup
CoMMIssIonIng
The Rotork CMA Range of actuators provide simple, safe and
rapid commissioning.
TooLs & eQuIpMenT ReQuIRed
(general guideline only)
Top Cover Fixings -
6mm Allen Wrench
Electrical Connections -
Terminal Screw Driver
Command & Feedback -
4 to 20 mA Command
source/meter
Actuator to Valve fixings - As Required.
CAuTIon
It is essential that the setup procedure is carried
out when the valve is not under working process
conditions, as full valve movement may occur.
IMpoRTAnT
It is essential that the actuator is mounted correctly to
the valve!
The height of the yoke or pillar and mounting plate, in
relation to the top of the valve spindle is critical to ensure
full stroke movement of the valve
.
The Installation & Setup will include the following steps:
1. Ensure valve position is noted and safe (Offline).
2. Actuator output shaft is retracted. (Linear Units only)
3. Actuator is in closed position. (Rotary Units only).
4. Mount and align actuator to valve.
5. Set limits of travel.
6. Configure control and indication parameters