Start-up
27
FA ROTEX HPSU compact 308 - 02/2012
3
Start-up
WARNING!
A ROTEX HPSU compact that is installed or started incorrectly may not operate properly and is dangerous for
the health and safety of individuals.
• The ROTEX HPSU compact may only be started up by authorised and trained heating experts.
CAUTION!
A ROTEX HPSU compact not put into operation properly can lead to damage to property and the environment.
• Observe the regulations in VDI 2035 in order to avoid corrosion and deposits.
• Measures for desalination, softening or hardness stabilization are necessary, if the filling and top-up water
have a high total hardness (>3 mmol/l - sum of the calcium and magnesium concentrations, calculated as
calcium carbonate).
– We recommend Fernox lime and corrosion protective agent
KSK (
15 60 50)
.
• During the plant operation, the water pressure at the manometer (green area) must be checked at regular
intervals. If necessary, readjust by refilling
3.1
Initial start-up
After the ROTEX HPSU compact was installed and connected completely, it will need to be undergo a one-time adaptation to the
installation environment to be carried out by technical personnel (configuration).
After this configuration is complete, the installation is ready for operation and the operator can make additional custom config-
urations on it.
The heating specialist must instruct the operator [on using the machine], must prepare the commissioning report, and fill out the
operating manual.
Setting up optional components such as a room thermostat or the ROTEX Solaris installation is carried out on the respective
component itself.
3.1.1 Requirements
– The ROTEX HPSU compact is fully connected.
– The heating and hot water system are filled and charged with the right pressure.
– The storage tank is filled to the overflow point.
– The heating system's control valves are open.
– The refrigerant system is dehumidified and filled with the specified amount of refrigerant.
– All electrical connections have been made in accordance with the Installation chapter.
– Optional accessories have been mounted on and connected up.
3.1.2 Configuration of DIP switches
WARNING!
To make changes to the DIP switch settings, the installation must first be disconnected from the power supply.
Î
Non compliance may cause damage to the HPSU compact.
• Check the DIP switch setting on the A1P circuit board of
the HPSU compact, adjust where necessary (see tab. 3-1).
DIP switch settings are not recognised until a
brief interruption to the power supply.
SS2
on
1 2 3 4
off
Fig. 3-1
Factory setting SS2