Fig. 3-11 Time behaviour of the floor function for coating heating (maximum temperature = 40 °C) - see legend in fig. 3-10
Fig. 3-12 Time behaviour of the floor function for function and coating heating (maximum temperature = 40 °C) - see legend in fig. 3-10
3
x
Start-up
32
FA ROTEX HPSU compact 308 - 02/2012
7. The following rework is still necessary, depending on the connection variant (see fig. 3-13 for the contact pin assignments)
and the floor function:
a) When connecting without wire jumpers:
• Set DIP switch SS2-3 to OFF.
• Set the desired flow temperature or activate weather-dependent set value regulation.
b) When connecting with wire jumpers:
• Set the desired flow temperature or activate weather-dependent set value regulation.
c) When connecting with room thermostat:
• Activate room thermostat.
• Set the desired flow temperature or activate weather-dependent set value regulation.
a)
b)
c)
Fig. 3-13 Connection options for heating/cooling contact for floor function