4
x
Parameter settings
48
FA ROTEX HPSU compact 308 - 02/2012
4.3
Additional control unit (HPRA1)
4.3.1 Overview of factory-set parameter settings
All parameters of the auxiliary control unit (HPRA1) are described in detail in a tabular overview of this section with the factory
settings and setting areas.
CAUTION!
If the commissioning parameters BOH... and BUH... are configured in such a way that operation with the backup
heater and/or the booster request is possible, it must first be ensured that power consumption cannot exceed
the permitted supply load.
Current peaks that occur when a network in the power supply network of the domestic installation fails, it can
cause material damage to electrical current consumers.
Menu item
Parameter
Designation
Access
Setting
range
Factory
setting
Increment
BE HF
start-up
INDOOR UNIT
Type of interior heat pump unit
0: Commissioning program not complete yet
1: HPSU compact 508
2: HPSU compact 516
3: HPSU compact 308
S
E
0
í
3
0
1
BOH type
Heat generator for hot water provision
(booster function)
(1
!
0: No heat generator for booster function
1: Electrical booster heater
2: Other booster heater
3: ROTEX G-plus
(1
If >0, the parameters [4], [5], [7] and [8] of the main control unit HPR1
are changed and changed as necessary.
0
í
3
0
1
BOH power
Heat output for the booster function in W
!
1000
í
12000 W
3000 W
100 W
BUH type
Heat generator for heating support (backup heater)
(2
!
0: No heat generator for backup function
1: Electrical backup heater
2: Other backup heater
3: ROTEX G-plus
(2
If >0, the parameters [4] and [5] of the main control unit HPR1 are
changed and changed as necessary.
0
í
3
0
1
BUH s1 power Heat output of backup heater with level 1 in W
!
1000
í
40000 W
3000 W
100 W
BUH s2 power Heat output of backup heater with level 2 in W
!
HZU
Heating support from hot water tank
0: No heating support from hot water tank
1: Solar heating support
(3
2: Other h eating support
(3
(3
If parameter is set to 1 or 2, then only heating support if T
DHW
> HZU
T Limit.
0
í
2
0
1
HZU T Limit
Temperature limit up to which the hot water tank may be dsi-
charged by HZU. Storage tank temperature sensor (T
DHW2
)
must be installed.
N
20
í
80 °C
50 °C
1 K