5.2.3 Checking and cleaning the burner
As a rule, the burner is wear-free. If you detect contamination or unsatisfactory combustion values, have a
Heating expert
dismantler, clean and possibly reset the burner (also refer to installation and maintenance instructions for the Expert).
Checking the burner
The burner inspection includes visual inspection of the burner condition as well as flue gas measurements. The checking of the
burner is done by the
Heating expert
as part of the legally specified flue gas check.
DANGER OF EXPLOSION!
Escaping gas is a direct threat to human health and life. Even a few sparks can cause major explosions.
• Only heating specialists trained and authorised by the gas or energy supply companies should be allowed
to work on gas systems.
In the course of maintenance work, safety-relevant components must also be checked to make sure that they
are achieving the nominal service life:
– CVBC automatic firing unit 10 years or 250.000 burner starts,
– Safety gas control block 10 years or 250.000 burner starts,
– Overpressure safety valve: 10 years.
We recommend completing the service log provided with all the measured values and the tasks performed, with
dates and signature.