6.3
Fault codes
Control THETA 23R
Tab. 6-2
Fault codes for the ROTEX GSU for control THETA 23R (detected from the central unit)
Fault code
Component/name
Fault
10-0
Outside temperature sensor
Interruption
10-1
Short circuit
12-0
Inflow temperature sensor, mixer circuit Interruption, mixer circuit pump is switched off, mixer motor is switched de-energised
12-1
Short circuit, mixer circuit pump is switched off, mixer motor is switched de-energised
13-0
Hot water storage tank temperature
sensor
Interruption
13-1
Short circuit
14-7
Modem contact
Fault signal
15-7
Burner blockage contact
Fault signal
16-0
Flue gas temperature sensor (if installed) Short circuit
16-1
Interruption
16-7
Fault signal
17-0
Return flow temperature sensor
Interruption
17-1
Short circuit
30-2
Burner
No switching off
30-3
No switching on
33-5
Flue gas temperature
Overshooting
70-0
Address
Address collision of the BUS subscribers
70-1
Activity
No T2B signal, check BUS cable and connections
70-6
Communication between control THETA
and CVBC automatic firing unit
Interruption
71-0
EEPROM
Internal fault
71-1
EEPROM faulty
Internal fault
Summary of Contents for GSU 320
Page 45: ...x Notes 45 BA ROTEX GSU 09 2007...